2010-08-04 13:15:50101 NORTH CLEMATIS STREET
 INTERIOR RENOVATION OF EXISTING SPACE
 PERMIT NUMBER 10070589
  
  
 1. WRONG LIFE SAFETY CODE REFERENCED ON SHEET A-001.
 SHOULD READ 2006 EDITION NOT 2007 EDITION.
  
 2. ALL WALK-IN COOLERS AND FREEZERS ARE TO BE FIRE
 SPRINKLER PROTECTED.
  
 3. AN EXIT SIGN APPEARS TO BE MISSING IN VESTIBULE ON
 PAGE E1.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY
 REMODELING OF THE FIRE SPRINKLER OR FIRE ALARM SYSTEM.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 6. REQUIRED EXIT DOORS SUBJECT TO OCCUPANT LOADS OF 100
 OR MORE PERSONS ARE TO BE EQUIPPED WITH PANIC HARDWARE.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED.
  
 7. FINAL OCCUPANT LOAD WILL BE DETERMINED BY THIS
 OFFICE. OCCUPANT LOAD WILL BE REQUIRED TO BE POSTED
 WHEN ESTABLISHED.
  
 8. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 9. DEBRIS SHALL BE REMOVED DAILY FROM THE SITE.
  
 10. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAIL FOR STAIRS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION