2010-08-04 13:15:50 | 101 NORTH CLEMATIS STREET | | INTERIOR RENOVATION OF EXISTING SPACE | | PERMIT NUMBER 10070589 | | | | | | 1. WRONG LIFE SAFETY CODE REFERENCED ON SHEET A-001. | | SHOULD READ 2006 EDITION NOT 2007 EDITION. | | | | 2. ALL WALK-IN COOLERS AND FREEZERS ARE TO BE FIRE | | SPRINKLER PROTECTED. | | | | 3. AN EXIT SIGN APPEARS TO BE MISSING IN VESTIBULE ON | | PAGE E1. | | | | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY | | REMODELING OF THE FIRE SPRINKLER OR FIRE ALARM SYSTEM. | | | | 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | 6. REQUIRED EXIT DOORS SUBJECT TO OCCUPANT LOADS OF 100 | | OR MORE PERSONS ARE TO BE EQUIPPED WITH PANIC HARDWARE. | | NO OTHER LOCKS OR LATCHES ARE PERMITTED. | | | | 7. FINAL OCCUPANT LOAD WILL BE DETERMINED BY THIS | | OFFICE. OCCUPANT LOAD WILL BE REQUIRED TO BE POSTED | | WHEN ESTABLISHED. | | | | 8. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | WITH NFPA 241. | | | | 9. DEBRIS SHALL BE REMOVED DAILY FROM THE SITE. | | | | 10. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS | | FOR HANDRAIL FOR STAIRS. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|