Plan Review Notes
Plan Review Notes For Permit 10070589
Permit Number 10070589
Review Stop B
Sequence Number 1
Notes
Date Text
2010-07-28 14:17:25BUILDING PLAN REVIEW
 PERMIT: 10070589
 ADD: 101 N CLEMATIS ST SUITE 100
 CONT: TO BE DETERMINED
 TEL: (305) 331-6194
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 JULY 28/ 2010
 1ST REVIEW
 ACTION: DENIED
  
 1) CONTRACTOR TO BE SIGNED ON TO VERIFY LICENSURE FL S
 489.
  
 2) PLEASE PROVIDE WIND DESIGN CRITERIA WITH ASSOCIATED
 PRESSURES: 1609.6.2 WIND DESIGN PROCEDURES
 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4. EXPOSURE "C"
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)/ ASCE 07
 FOR BUILDINGS OVER 60'-0" TALL.
  
 2.5 ) POSSITIVE & NEGATIVE PRESSURES.
  
 3) IT APPEARS THAT THE FL 13380 BP GLASS SECTIONAL
 GARAGE DOOR, DESIGN PRESSURE +/- 50.0 AT 44" X 94"=
 4136 SQ INCHES/ 28.72 SQ FT WILL HAVE A MUCH HIGHER
 PRESSURE AT 60'
 THE PRESSURES ARE APPROXIMATELY -63.8/ +58.5 HIGHER
 THAN ALLOWED BY THIS PRODUCT APPROVAL.
  
 4) SHEET A-100 MEZZANINE LEVEL STORAGE ROOM# 113.
 PLEASE INDICATE THE LIVE LOAD THAT THE MEZZANINE WAS
 DESIGNED AS PER FBC-B TABLE 1607.1(37)
  
 5) SHEET A-100 THE MEZZANINE LEVEL PLEASE COMPLY WITH:
 5A) 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES.
 IT SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND GROUP F
 OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR
 LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD
 CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY
 AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE
 SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER
 SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BLDG DEPT.
  
 5B) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART
 OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS
 PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE
 BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON
 PLATES OF APPROVED DESIGN WHICH SHALL BE SUPPLIED &
 SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A
 CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE.
 SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM.
  
 5C) THE PLANS ARE NOT CLEAR AS TO THE PURPOSE OF THE
 OTHER HORIZONTAL FRAMING AREAS, SEE 3-D FRAMING
 DIAGRAMS ON A-140 AND THTE CEILING OF THE RESTROOM WILL
 ONLY BE USED AS A CEILING AND NOT AS A OCCUPIABLE
 LEVEL. THESE AREAS COULD BE VIEWED AS OCCUPIABLE
 LEVELS, POSSIBLY ADDITIONAL DANCE FLOOR AREAS. PLEASE
 PROVIDE NOTATION ON THE PLANS AS TO THE INTENDED USE.
 106.1.2 ADDITIONAL INFORMATION REQUIRED!
  
 6) A-131 & A-140 BOTH INDICATE A NEW STAIR DESIGN
 PLEASE PROVIDE:
 6A) PROVIDE THE DESIGN LIVE LOADS FOR THE STAIR PER
 FBC-B TABLE 1607.1(36) 100 PSF. SHOP DRAWING MAY FOLLOW
 AFTER PERMIT IS ISSUED ONCE REVIEWED BY THE DESIGNER OF
 RECORD, TO BE SUBMITTED TO THE BUILDING DEPARTMENT.
  
 6B) PLANS WILL ALSO NEED TO PROVIDE THE MINIMUM DESIGN
 CRITERIA FOR THE STAIR RISE AND RUN IN COMPLIANCE WITH
 FBC-B 1009.3. SHOP DRAWING MAY FOLLOW AFTER PERMIT IS
 ISSUED ONCE REVIEWED BY THE DESIGNER OF RECORD, TO BE
 SUBMITTED TO THE BUILDING DEPARTMENT.
  
 7) SHEET A-140 KEY NOTE S-60 INDICATES THE USE OF A
 C8X18.7 STEEL C CHANNEL, IS THIS A SINGLE MEMBER OR 2
 MEMBERS FORMING A BOXED HEADER CONFIGURATION SINCE THE
 SIMPSON S/BA HANGERS ARE LOCATED ON BOTH SIDES? 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 8) SHEET A-400 KEY NOTE# 2 INDICATES THE USE OF WOOD
 BLOCKING, PLEASE REVISE TO FIRE RETARDENT TREATED PER
 FBC-B 603.1.
  
 9) A-400 FINISH SCHEDULE FOR ROOM 105 & 106 MENS &
 LADIES RESTROOMS INDICATE PAINTED WALLS PLEASE REVIEW
 SECTION FBC-B 1210.2 WALLS. WALLS WITHIN 2 FEET (610
 MM) OF URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219
 MM) ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 10) PLEASE LOCATE ON SHEET A-100 THE POTABLE FIRE
 EXTINGUISHERS PER FBC-B 906.1.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
 8) SHEET A-100 & A-300 BOTH INDICATE BELOW TTHE
 MEZZANINE LEVEL A WALK IN COOLER PLEASE PROVIDE DETAILS
 AS TO WHERE THE FLOOR /CEILING INSULATION WILL BE
 LOCATED AND PROVIDE COMPLIANCE WITH FBC-B 2603.4.1.2
 COOLER & FREEZER WALLS.
  
 9)


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved