2011-04-18 09:46:17 | BUILDING PLAN REVIEW |
| PERMIT: 10070561 |
| ADD: 716 NEY YORK ST |
| CONT: TO BE DETERMINED |
| CONTACT: PENE LATHAM |
| TEL: (561)832-1500 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 4TH REVIEW |
| ACTION: DENIED |
| |
| |
| 1-3) COMPLIED. |
| |
| |
| 4) 106.3.3 THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| REPORTS ARE AS FOLLOWS: |
| 5A) COMPLIED.WINDOWS/ SINGLE HUNG - RULE 9B-72(31) (B) |
| NOA 080820.14 |
| WINDOWS/ CASEMENT RULE 9B-72(31) (B) NO APPROVALS WERE |
| SUBMITTED |
| |
| 5B) COMPLIED.EXTERIOR DOORS RULE 9B-72(31) (A) NEW RULE |
| 9N-3 FL 4334.1 |
| 5C) ROOF ASSEMBLIES RULE 9B-72(31) (D) NEW RULE 9N-3 NO |
| APPROVALS WERE SUBMITTEDCAN BE ISSUED UNDER A SEPERATE |
| ROOFING PERMIT. |
| 5D) NOT REQUIRED |
| |
| PLEASE NOTE IF THE CONTRACTOR DOES NOT SUPPLY THE |
| PRODUCT APPROVALS BEFORE TIME OF ISSUANCE, THESE ITEMS |
| CAN BE A BUILDING PROVISO: WHICH MEANS THE PRODUCT |
| APPROVALS CAN BE BROUGHT IN AFTER ISSUANCE BUT WILL BE |
| CONSIDERED A REVISION WITH FURTHER REVIEW AND |
| ASSOCIATED FEES. THE DESIGN PRESSURES INDICATED ON |
| SHEET 5.1 ARE CORRECT. |
| |
| 6-8) COMPLIED. |
| |
| 9) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS. |
| N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL |
| BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION |
| AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD |
| A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO |
| COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE |
| MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE |
| BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2. |
| N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN |
| APPLICABLE (SEE SECTION N1100.7.3), MEET THE |
| PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR |
| INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND |
| EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING |
| RETROFITTED OR REPLACED. |
| |
| 10) IMPACT FEES : COMPLIED. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |