Plan Review Notes
Plan Review Notes For Permit 10070561
Permit Number 10070561
Review Stop M
Sequence Number 3
Notes
Date Text
2011-03-30 08:42:10MECHANICAL PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE- MECHANICAL
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS.
 N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL
 BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION
 AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD
 A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO
 COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE
 BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2.
 N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN
 APPLICABLE (SEE SECTION N1100.7.3), MEET THE
 PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND
 EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING
 RETROFITTED OR REPLACED.
  
 2) SHEET 6.1 MECHANICAL SHEET IS MISSING THE A/C SYSTEM
 DESIGN DATA, BLANK!
  
  
 JAMES A. WITMER C.B.O.
 SFP-100
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731