Plan Review Notes For Permit 10070561 |
Permit Number |
10070561 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-02-03 11:15:58 | MECHANICAL PLAN REVIEW | | PERMIT: 10070561 | | ADD: 716 NEY YORK ST | | CONT: TO BE DETERMINED | | CONTACT: PENE LATHAM | | TEL: (561)832-1500 | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE- MECHANICAL | | W/ 2009 FBC SUPPLEMENTS | | * WEST PALM BEACH AMENDMENTS | | | | 2ND REVIEW | | ACTION: DENIED | | | | 1) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS. | | N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL | | BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION | | AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD | | A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO | | COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE | | MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE | | BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2. | | N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN | | APPLICABLE (SEE SECTION N1100.7.3), MEET THE | | PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR | | INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND | | EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING | | RETROFITTED OR REPLACED. | | | | 2) SHEET 6.1 MECHANICAL SHEET IS MISSING THE A/C SYSTEM | | DESIGN DATA, BLANK! | | | | | | JAMES A. WITMER C.B.O. | | SFP-100 | | COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: (561)805-6715 | | FAX:(561)805-6731 | | E-MAIL: [email protected] | | | | CONSTRUCTION SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
|