Notes
Date Text
2011-02-03 11:09:15A SEPERATE GAS PERMIT WILL BE REQUIRED NOT TO BE
 INCLUDED UNDER THE MASTER.
  
 REQUIRED INFORMATION FOR GAS PERMIT:
  
 1) PLEASE PROVIDE THE DEVELOPED LENGTH OF THE GAS
 PIPING FROM THE METER TO THE LAST APPLIANCE, BTU OF
 EACH APPLIANCE.
  
 1A) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE.
 SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER),
 TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER FBC-2007 FUEL
 GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 1B) 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED,
 ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL TUBING FOR EACH
 PIPE SIZE IF BEING USED.
  
 1C) NEW GAS INSTA-HOT WATER HEATER PLEASE PROVIDE
 MANUFACTURERS SPEC FOR BTU, AND APPROVAL FOR EXTERIOR
 LOCATIONS. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2007 FUEL GAS CODE SEC 402.2 &
 RESIDENTIAL CODE SEC. G2413.2.
  
 1D) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8 THRU 402.6.1 AND
 TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8).
  
 1E) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2004
 FUEL GAS CODE SEC. 402.2. NATURAL GAS SPECIFY .5 PSI OR
 2 PSI.
  
  
  