Date |
Text |
2011-02-03 11:09:15 | A SEPERATE GAS PERMIT WILL BE REQUIRED NOT TO BE |
| INCLUDED UNDER THE MASTER. |
| |
| REQUIRED INFORMATION FOR GAS PERMIT: |
| |
| 1) PLEASE PROVIDE THE DEVELOPED LENGTH OF THE GAS |
| PIPING FROM THE METER TO THE LAST APPLIANCE, BTU OF |
| EACH APPLIANCE. |
| |
| 1A) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR |
| 2007 FUEL GAS CODE. |
| SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER), |
| TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER FBC-2007 FUEL |
| GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| 1B) 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, |
| ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL TUBING FOR EACH |
| PIPE SIZE IF BEING USED. |
| |
| 1C) NEW GAS INSTA-HOT WATER HEATER PLEASE PROVIDE |
| MANUFACTURERS SPEC FOR BTU, AND APPROVAL FOR EXTERIOR |
| LOCATIONS. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND THE FBC-2007 FUEL GAS CODE SEC 402.2 & |
| RESIDENTIAL CODE SEC. G2413.2. |
| |
| 1D) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| ON THE SYSTEM. REFER TO |
| THE FBC-2007 FUEL GAS CODE SECS. 401.8 THRU 402.6.1 AND |
| TABLES 402.4(1) THRU |
| 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU |
| G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). |
| |
| 1E) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2004 |
| FUEL GAS CODE SEC. 402.2. NATURAL GAS SPECIFY .5 PSI OR |
| 2 PSI. |
| |
| |
| |