| MECHANICAL PLAN REVIEW |
| PERMIT: 10070561 |
| ADD: 716 NEY YORK ST |
| CONT: TO BE DETERMINED |
| CONTACT: PENE LATHAM |
| TEL: (561)832-1500 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE- MECHANICAL |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| |
| 1) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS. |
| N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL |
| BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION |
| AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD |
| A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO |
| COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE |
| MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE |
| BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2. |
| N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN |
| APPLICABLE (SEE SECTION N1100.7.3), MEET THE |
| PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR |
| INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND |
| EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING |
| RETROFITTED OR REPLACED. |
| |
| 2) PROVISO: M1602.4 BALANCED RETURN AIR. RESTRICTED |
| RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS ARE LOCATED |
| IN CENTRAL ZONES AND CLOSED INTERIOR DOORS IMPEDE AIR |
| FLOW TO THE RETURN GRILL OR WHEN CEILING SPACES ARE |
| USED AS RETURN PLENUMS AND FIRE WALLS RESTRICT AIR |
| MOVEMENT FROM ONE PORTION OF THE RETURN PLENUM TO |
| ANOTHER. PROVISIONS SHALL BE MADE IN RESIDENTIAL |
| BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND PRESSURE |
| DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR. PRESSURE |
| DIFFERENTIALS ACROSS CLOSED DOORS WHERE RETURNS ARE |
| CENTRALLY LOCATED SHALL BE LIMITED TO 0.01 INCH WC (2.5 |
| PA) OR LESS. PRESSURE DIFFERENTIALS ACROSS FIRE WALLS |
| IN CEILING SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH |
| WC (2.5 PA) BY PROVIDING AIR DUCT PATHWAYS OR AIR |
| TRANSFER PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE |
| LOW ZONE. |
| |
| EXCEPTIONS: |
| |
| 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR |
| HAVING AT LEAST AN UNRESTRICTED 1 INCH (25 MM) UNDERCUT |
| TO ACHIEVE PROPER RETURN AIR BALANCE. |
| |
| |