Plan Review Notes
Plan Review Notes For Permit 10070561
Permit Number 10070561
Review Stop M
Sequence Number 1
Notes
Date Text
2010-08-12 11:23:18 
  
  
  
  
 MECHANICAL PLAN REVIEW
 PERMIT: 10070561
 ADD: 716 NEY YORK ST
 CONT: TO BE DETERMINED
 CONTACT: PENE LATHAM
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE- MECHANICAL
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS.
 N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL
 BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION
 AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD
 A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO
 COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE
 BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2.
 N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN
 APPLICABLE (SEE SECTION N1100.7.3), MEET THE
 PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND
 EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING
 RETROFITTED OR REPLACED.
  
 2) PROVISO: M1602.4 BALANCED RETURN AIR. RESTRICTED
 RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS ARE LOCATED
 IN CENTRAL ZONES AND CLOSED INTERIOR DOORS IMPEDE AIR
 FLOW TO THE RETURN GRILL OR WHEN CEILING SPACES ARE
 USED AS RETURN PLENUMS AND FIRE WALLS RESTRICT AIR
 MOVEMENT FROM ONE PORTION OF THE RETURN PLENUM TO
 ANOTHER. PROVISIONS SHALL BE MADE IN RESIDENTIAL
 BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND PRESSURE
 DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR. PRESSURE
 DIFFERENTIALS ACROSS CLOSED DOORS WHERE RETURNS ARE
 CENTRALLY LOCATED SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PA) OR LESS. PRESSURE DIFFERENTIALS ACROSS FIRE WALLS
 IN CEILING SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH
 WC (2.5 PA) BY PROVIDING AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE
 LOW ZONE.
  
 EXCEPTIONS:
  
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCH (25 MM) UNDERCUT
 TO ACHIEVE PROPER RETURN AIR BALANCE.
  
  