2010-09-02 11:40:34 | 600 VILLAGE BOULEVARD |
| RENEGADES |
| PERMIT NUMBER 10070434 |
| |
| |
| 1. ON AUGUST 31, 2010, REPRESENTATIVES OF THE FIRE |
| MARSHAL'S OFFICE MET WITH PETE RUSSO, ARCHITECT TO |
| DISCUSS EXITING ISSUES FOR THE ESTABLISHMENT. A NEW |
| LIFE SAFETY PLAN WAS SUBMITTED LATER IN THE DAY ON |
| AUGUST 31, 2010 WHICH DISPLAYED NEW EXIT SIGNS AND |
| EMERGENCY LIGHTS AND ALSO A NEW EXIT OPENING HAS BEEN |
| PROVIDED FOR NEAR BAR # 2. ALSO DOORS HAVE BEEN REMOVED |
| APPROACHING THE HOST STAND WHICH APPEARS TO ACCOMMODATE |
| THE 2/3 REQUIRED EXIT CAPACITY FOR THE ESTABLISHMENT. |
| |
| 2. AS NOTED ON THE NEW LIFE SAFETY PLAN, SEPARATE PLANS |
| AND PERMITS REQUIRED FOR THE FIRE SPRINKLER, FIRE |
| ALARM, HOOD SUPPRESSION, AND GREASE HOOD EXHAUST |
| SYSTEMS. |
| |
| 3. CROWD MANAGEMENT CERTIFICATES FROM MANAGEMENT |
| PERSONNEL ARE TO BE SUBMITTED TO THE FIRE MARSHAL'S |
| OFFICE PRIOR TO OPENING. |
| |
| 4. THE MAXIMUM OCCUPANT LOAD WILL BE ESTABLISHED BY THE |
| FIRE MARSHAL'S OFFICE AND SHALL BE POSTED. THIS LEGAL |
| OCCUPANT LOAD IS NOT TO BE EXCEEDED FOR ANY REASON. |
| |
| 5. WHEN THE FIRE ALARM SYSTEM SHOP DRAWINGS ARE |
| SUBMITTED, PLEASE INDICATE ON THESE PLANS WHAT |
| EMERGENCY INSTRUCTIONS WILL BE PROVIDED TO OCCUPANTS. |
| |
| 6. ALL EXIT DOORS THAT ARE SUBJECT TO LOADS OF 100 OR |
| MORE PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE. |
| |
| 7. THE LIGHTING PLAN SHEET 2.0E WILL NEED TO BE CHANGED |
| TO MATCH THE REVISED LIFE SAFETY PLAN. |
| |
| 8. GAS INSTALLATIONS SHALL COMPLY WITH THE APPLICABLE |
| NFPA STANDARDS AND BE INSTALLED IN A SAFE AND |
| WORKMANLIKE MANNER. |
| |
| |
| APPROVED PROVISO |
| |
| |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |
| |
| |
| |