2010-07-28 10:16:19PLUMBING PLAN REVIEW #1
 DENIED:
  
 1. A UNISEX TOILET ROOM WILL BE REQUIRED.
 FBC PLUMBING 2007 403.7 UNISEX TOILET AND BATHING
 ROOMS. IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN
 ACCESSIBLE UNISEX TOILET ROOM SHALL BE PROVIDED WHERE
 AN AGGREGATE OF SIX OR MORE MALE AND FEMALE WATER
 CLOSETS IS REQUIRED.
  
 2. PLEASE SHOW CALCULATIONS FOR GREASE INTERCEPTOR
 CAPACITY FROM TABLE 1003.3.4.1 OR 1003.5.1. BELOW IS AN
 EXAMPLE FROM THE PLUMBING CODE
 TABLE 1003.5.1 SIZING FORMULAS FOR GREASE INTERCEPTORS
 PRIVATE SEWAGE DISPOSAL SYSTEM
 SIZING FORMULA FOR RESTAURANTS:
 (S) X (GS) X (HR/12 X (LF) = EFFECTIVE CAPACITY OF
 GREASE INTERCEPTOR IN GALLONS
 WHERE:
 S = NUMBER OF SEATS IN DINING AREA
 GS = GALLONS OF WASTE WATER PER SEAT (USE 25 GALLONS
 FOR RESTAURANTS WITH CHINA DISHES AND/OR AUTOMATIC
 DISHWASHER) (USE 10 GALLONS FOR RESTAURANTS WITH PAPER
 OR BASKETS AND NO DISHWASHERS)
 HR = NUMBER OF HOURS RESTAURANT IS OPEN
 LF = LOADING FACTOR (USE 2.00 INTERSTATE HIGHWAY; 1.50
 OTHER FREEWAYS; 1.25 RECREATIONAL AREA; 1.00 MAIN
 HIGHWAY; 0.75 OTHER HIGHWAY)
  
 ******NOTE: FOR OTHER THAN PRIVATE SEWAGE DISPOSAL
 SYSTEMS, REDUCE GALLON VALUES BY 25 PERCENT.******
  
 3. COLD WATER DROP IN WOMENS ROOM FOR THE 4 WC'S WOULD
 BE 1 1/4" USING TABLE 603.1
  
 4. COLD WATER DROP IN MENS ROOM SHOULD BE 1 1/4" USING
 TABLE 603.1, ALSO THE ADA WC AND LAV ARE MISSING FROM
 THE ISOMETRIC.
  
 5. THE REGULAR WC IN THE MENS ROOM IS NOT VENTED.
  
 6. ALL FLOOR DRAINS WILL REQUIRE TRAP PRIMERS EXCEPT
 THOSE THAT ARE RECEIVING DRAINAGE FROM FLOOR SINKS.
  