2010-07-28 10:16:19 | PLUMBING PLAN REVIEW #1 |
| DENIED: |
| |
| 1. A UNISEX TOILET ROOM WILL BE REQUIRED. |
| FBC PLUMBING 2007 403.7 UNISEX TOILET AND BATHING |
| ROOMS. IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN |
| ACCESSIBLE UNISEX TOILET ROOM SHALL BE PROVIDED WHERE |
| AN AGGREGATE OF SIX OR MORE MALE AND FEMALE WATER |
| CLOSETS IS REQUIRED. |
| |
| 2. PLEASE SHOW CALCULATIONS FOR GREASE INTERCEPTOR |
| CAPACITY FROM TABLE 1003.3.4.1 OR 1003.5.1. BELOW IS AN |
| EXAMPLE FROM THE PLUMBING CODE |
| TABLE 1003.5.1 SIZING FORMULAS FOR GREASE INTERCEPTORS |
| PRIVATE SEWAGE DISPOSAL SYSTEM |
| SIZING FORMULA FOR RESTAURANTS: |
| (S) X (GS) X (HR/12 X (LF) = EFFECTIVE CAPACITY OF |
| GREASE INTERCEPTOR IN GALLONS |
| WHERE: |
| S = NUMBER OF SEATS IN DINING AREA |
| GS = GALLONS OF WASTE WATER PER SEAT (USE 25 GALLONS |
| FOR RESTAURANTS WITH CHINA DISHES AND/OR AUTOMATIC |
| DISHWASHER) (USE 10 GALLONS FOR RESTAURANTS WITH PAPER |
| OR BASKETS AND NO DISHWASHERS) |
| HR = NUMBER OF HOURS RESTAURANT IS OPEN |
| LF = LOADING FACTOR (USE 2.00 INTERSTATE HIGHWAY; 1.50 |
| OTHER FREEWAYS; 1.25 RECREATIONAL AREA; 1.00 MAIN |
| HIGHWAY; 0.75 OTHER HIGHWAY) |
| |
| ******NOTE: FOR OTHER THAN PRIVATE SEWAGE DISPOSAL |
| SYSTEMS, REDUCE GALLON VALUES BY 25 PERCENT.****** |
| |
| 3. COLD WATER DROP IN WOMENS ROOM FOR THE 4 WC'S WOULD |
| BE 1 1/4" USING TABLE 603.1 |
| |
| 4. COLD WATER DROP IN MENS ROOM SHOULD BE 1 1/4" USING |
| TABLE 603.1, ALSO THE ADA WC AND LAV ARE MISSING FROM |
| THE ISOMETRIC. |
| |
| 5. THE REGULAR WC IN THE MENS ROOM IS NOT VENTED. |
| |
| 6. ALL FLOOR DRAINS WILL REQUIRE TRAP PRIMERS EXCEPT |
| THOSE THAT ARE RECEIVING DRAINAGE FROM FLOOR SINKS. |
| |