2010-08-11 10:52:36PLANS DENIED
 1) ADDRESS ON PLANS AND APPLICATION DO NOT MATCH .
 2) EXHAUST FOR WOMAN'S BATHROOM SHALL BE A MINIMUM OF
 350 CFM PER TABLE 403.3 2007 FBC (M)
 3) SEPARATE PLANS AND PERMIT ARE REQUIRED FOR THE HOOD.
 4) PLEASE REFER TO SECTION 506.3.12.3 TERMINATION
 LOCATION OF EXHAUST OUTLETS.