Plan Review Notes For Permit 10070434 |
Permit Number |
10070434 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-07-28 10:58:25 | GAS PLAN REVIEW #1 | | DENIED: | | | | 1. WATER HEATER REQUIRES 1 1/4" PIPE UP TO THE | | CONNECTOR TABLE 402.4(2) | | | | 2. PLEASE SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | NFPA 58, AND FBC-2007 FUEL GAS SEC. 402.2 | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|