Plan Review Notes
Plan Review Notes For Permit 10070434
Permit Number 10070434
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-07-26 12:06:44INTERIOR REMODEL OF EXISTING TGIF RESTARAUNT TO NEW
 RESTAURANT AND BAR PER CONSTRUCTION DOCUMENTS
 PERMIT NUMBER 10070434
  
 1. FLOOR PLAN DOES NOT ILLUSTRATE ANY SEATING FOR
 PHYSICALLY CHALLENGED PERSONS. PLEASE ILLUSTRATE THESE
 SEATING LOCATIONS.
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 3. THE BUILDING HAS BEEN VACANT FOR SEVERAL YEARS. ALL
 EXISTING SYSTEMS AND DEVICES THAT ARE TO REMAIN ARE TO
 BE THOROUGHLY INSPECTED BY LICENSED CONTRACTORS TO
 ENSURE SUITABILITY FOR CONTINUED USE. PROPER
 DOCUMENTATION IS REQUIRED TO BE SUBMITTED TO THIS
 OFFICE.
  
 4. BASED ON ASSUMED OCCUPANT LOADS, CROWD MANAGEMENT
 TRAINING WILL BE REQUIRED FOR MANAGEMENT STAFF. PLEASE
 GO TO THE MARYLAND STATE FIRE MARSHALS OFFICE WEB-SITE
 AND CLICK ON THE CROWD MANAGEMENT TRAINING ICON. STAFF
 MEMBERS ARE TO WATCH THE VIDEO, TAKE THE ONLINE TEST,
 AND SUBMIT CERTFIICATES TO THIS OFFICE.
  
 5. PLEASE DISPLAY CIRCULATION PATHS THAT WILL BE USED
 FOR EXIT ACCESS PURPOSES WITHIN THE ESTABLISHMENT.
  
 6. THE REQUIRED FIRE ALARM SYSTEM SHALL BE CAPABLE OF
 PROVIDING VOICE EVACUATION MESSAGES WHEN THE FIRE ALARM
 OR FIRE SPRINKLER SYSTEM HAS ACTIVATED. PLEASE PROVIDE
 SEPARATE PLANS AND PERMITS FOR ANY FIRE SPRINKLER OR
 FIRE ALARM SYSTEM REMODELING.
  
 7. ALL WALK-IN COOLERS AND FREEZERS ARE TO BE FIRE
 SPRINKLER PROTECTED.
  
 8. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEMS. THE FIRE
 SUPPRESSION SYSTEM FOR THE HOOD AND DUCT SHALL MEET THE
 REQUIREMENTS OF UL 300.
  
 9. BUILDING ADDRESS IS REQUIRED. A MINIMUM OF AT LEAST
 6" HIGH NUMBERS ARE REQUIRED.
  
 10. NO FIRE SPRINKLER SYSTEM DETAILS PROVIDED WITH
 DRAWINGS.
  
 11. ANY BUILDING THAT HAS A LIGHT WEIGHT ROOF OR LIGHT
 WEIGHT FLOOR TRUSS SHALL BE PROPERLY PLACARDED AS PER
 FLORIDA STATUE. PLEASE VERIFY THAT THIS FACILITY DOES
 NOT REQUIRE THIS PLACARDING.
  
 12. A KNOX-BOX IS REQUIRED. PLEASE CONTACT THE KNOX
 COMPANY AT WWW.KNOXBOX.COM TO ORDER THE KEY BOX IF ONE
 DOES NOT CURRENTLY EXIST.
  
 13. PLEASE INDICATE LOCATIONS OF PORTABLE FIRE
 EXTINGUISHING EQUIPMENT.
  
 14. PLEASE ILLUSTRATE ALL LOCATIONS OF FIRE ALARM
 SIGNALING AND NOTIFICATION APPLIANCES.
  
 15. FINAL OCCUPANT LOAD WILL BE DETERMINED BY THIS
 OFFICE.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION