Plan Review Notes
Plan Review Notes For Permit 10070434
Permit Number 10070434
Review Stop B
Sequence Number 1
Notes
Date Text
2010-07-27 10:08:59BUILDING PLAN REVIEW
 PERMIT: 10070434
 ADD: 600 VILLAGE BLVD
 CONT: 3-D HOMES INC
 TEL: (561)662-9327
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) THE LIFE SAFETY PLAN 1.8A PLEASE IDENTIFY THE AREA
 BY BAR# 4 IT APPEARS TO BE A RAMP. SHEET 1.9A THERE
 APPEARS TO BE A 3 INCH DIFFERENCE IN HEIGHT AND THIS
 AREA IS LABELED A RAMP.
 PLEASE IDENTIFY THE RAMP AS SUCH.
 1B) SHEET 1.1A THERE APPEARS TO BE SOME TYPE OF
 EQUIPMENT LABELED # 71 A UNDER BAR PASS THRU- SERVICE
 STATION, THIS APPEARS TO BE BLOCKING THE AISLE,
 PROTRUDING OBJECTS, 11-4.4.1.
 PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR WIDTH OF
 AN ACCESSIBLE ROUTE OR MANEUVERING SPACE [SEE FIGURE
 8(E)].
  
 2) SHEET 1.7A CUT SECTION 2/1.3A AND NOTE# 4, 36"
 OPENING WITH WOOD CAP. THE DETAIL INDICATES A NEW 6
 INCH METAL STUD WALL ON SIX INCH CURB. THE PLANS DO NOT
 INDICATE IN THIS SECTION HOW THE CURB IS TO BE ANCHORED
 TO THE SLAB AND BE PART OF TTHE MWFRS. THE SECOND ISSUE
 WITH THIS DETAIL IS NO CLARIFICATION IF THE PLYWOOD
 SHEATHING IS TO STOP AT THE BOTTOM METAL TRACK OR TO GO
 TO THE SLAB HEIGHT. 2304.11.2.6 WOOD SIDING. CLEARANCE
 BETWEEN WOOD SIDING AND EARTH ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM)
 EXCEPT WHERE SIDING, SHEATHING AND WALL FRAMING ARE OF
 NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD.
  
 3) THIS SAME SECTION ALSO INDICATES THTE USE OF WIRE
 LATH AND STUCCO, PLEASE REFER TO FBC-B 1404.2.1
 1404.2.1 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED
 TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL BE
 TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER AND
 THE WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE
 PROVIDED BETWEEN THE WATER RESISTIVE BARRIER AND THE
 CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE
 FOLLOWING:
  
 3.1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER
 OR
  
 3.2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP, OR
  
 3.3 OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 4) PLEASE IDENTIFY HOW THE TOP AND BOTTOM TRACKS ARE TO
 BE FASTENED & SPACING TO THE STRUCTURE TO BACOME PART
 OF THE MWFRS.
  
 5) SHEET 1.7A NOTE # 6 INDICATES THE RELOCATION OF AN
 EXISTING BILCO HATCH, IS THE LOCATION ON THIS PLAN THE
 CURRENT LOCATION OR THE NEW LOCCATION, AND WHAT TYPE OF
 FRAMING IS TO BE REQUIRED FOR BLOCKING AND TYPE OF
 FASTENERS AND SPACING. THIS IS PART OF COMPONENTS AND
 CLADDING, PLEASE INCLUDE PRESSURES FOR ROOF ZONE WHERE
 THE ROOF HATCH IS LOCATED.
  
 6) SHEET 1.7A LOCATED AT BAR# 2 AND TO THE RIGHT OF BAR
 # 2 THERE ARE TO CONSTRUCTION NOTE SYMBOLS # 1
 INDICATING THE REPLACEMEN OF FIXED WINDOWS, IS THIS A
 TYPO? 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 7) SHEET 1.4A SECTION# 1 INDICATES A 42 INCH HIGH DRINK
 RAIL ON POST, PLEASE REVIEW SECTION 11-4.4.1
 FREE-STANDING OBJECTS MOUNTED ON POSTS OR PYLONS MAY
 OVERHANG 12 IN (305 MM) MAXIMUM FROM 27 INCHES TO 80
 INCHES (685 MM TO 2030 MM) ABOVE THE GROUND OR FINISHED
 FLOOR [SEE FIGURE 8(C) AND FIGURE 8(D)].
  
 8) SHEET 1.4A AND 1.6A THERE APPEARS TO BE A LIGHT
 TRUSS THAT HANGS FROM THE ROOF FRAMING ABOVE, PLEASE
 IDENTIFY THE TYPE OF ROOF STRUCTURE THAT EXIST, WOOD
 TRUSSES OR STEEL BAR JOIST?
 HOW THE LIGHT TRUSS WILL BE ATTACHED TO THE ROOF
 FRAMING STRUCTURE AND THE ADDITIONAL LOADS THAT WILL
 OCCUR, WILL THIS POINT LOADING REQUIRE ADDITIONAL
 STRENGTHING OF THE EXISTING ROOF FRAMING SYSTEM?
  
 9) THE PLANS INDICATE THE USE OF NEW WALK IN FREEZERS
 AND COOLER, PLEASE PROVIDE MANUFACTURERS SPEC IN
 COMPLIANCE WITH FBC-B 2603.4.1.2.
  
 10) PLEASE PROVIDE ON THE LIFE SAFETY PLAN COMPLIANCE
 WITH 11-5.1- 11-5.3.
  
 11) ADDITIONAL INFORMATION REQUIRED 106.1.2. SHEET 2.2E
 PANEL D INDICATES ON CIRCIUT# 5 A ALARM/ PHONE. IS THIS
 A FIRE ALRM SYSTEM OR BURGALAR ALARM SYSTEM? FBC-B WITH
 OCCUPANT LOADS OF 300 OR MORE UNDER ASSEMBLY A MANUAL
 FIRE ALARM SYSTEM WOULD BE REQUIRED 907.2.1.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved