Plan Review Notes
Plan Review Notes For Permit 10070389
Permit Number 10070389
Review Stop B
Sequence Number 3
Notes
Date Text
2010-09-21 09:59:59BUILDING PLAN REVIEW
 PERMIT: 08010251/ REV 10070389
 ADD: 2223 PALM BEACH LAKES # 101
 CONT: CONFORT BUILDERS
 TEL: (561)662-2455
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 SEPTEMBER 21/2010
 3RD REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
  
 1A)SEMI-COMPLIED. PLEASE PROVIDE A SITE PLAN WITH THE
 NEW EGRESS DOORS AT SIDE OF BUILDING INDICATING THE
 ACCESSIBLE PATH TO THE PUBLIC WAY. 11-4.1.3(8)(A)(II)
 ACCESSIBLE ENTRANCES MUST BE PROVIDED IN A NUMBER AT
 LEAST EQUIVALENT TO THE NUMBER OF EXITS REQUIRED BY THE
 APPLICABLE BUILDING/FIRE CODES. THE EXTERIOR DOORS FROM
 HALL'S 3 & 4 ARE MISSING ON THE DEVELOPED PLAN DATED
 8/23/2010. WITH THE ACCORDIAN DOORS IN THE CLOSED
 POSITION THESE ROOMS ALL HAVE AN OCCUPANT LOAD GREATER
 THAN 50 OCCUPANTS REQUIRING 2 MEANS OF EGRESS. FBC-B
 1015.1(1).
  
 THE PLANS ARE NOT CONSISTENT IN INDICATING THE NEW
 RECESSED EXIT ENCLOSURES:
 A-1 SCOPE OF WORK THE NEW RECESSED EXIT ENCLOSURES ARE
 MISSING
 A-3 THE LIFE SAFETY PLAN THEY ARE MISSING AND THE
 ADDITIONAL EXIT SIGNAGE.
 A-4 THE REFLECTED CEILING PLAN THE ENCLOSURES ARE
 MISSING AND EXIT SIGNAGE ,
 NOTE NO STRUCTURAL INFORMATION WAS PROVIDED FOR THE NEW
 RESSED ENCLOSURE, PRODUCT APPROVAL FOR DOOR
 E-1 ALSO IS EFFECTED WITH THE ADDITIONAL EXIT LIGHT
 REQUIREMENTS.
  
 1B-G-I) COMPLIED.
  
 1J) SECOND REQUEST,PLANS ALSO INDICATE ON A-2 A NEW
 STOREFRONT DOOR AND WINDOW SYSTEM, PLEASE PROVIDE WIND
 DESIGN CRITERIA:
  
 1609.6.2 WIND DESIGN PROCEDURES
 1J)(1) COMPLIED.
  
 1J)(2)COMPLIED.
  
 1J)(3) SECOND REQUEST, AN EXPOSURE CATEGORY SHALL BE
 DETERMINED IN ACCORDANCE WITH 1609.4. SHEET A-1
 (8/23/10) INDICATES A "B" EXPOSURE, PLEASE REVIEW
 SECTION
 FBC-B 1609.4.3 EXPOSURE C THIS EXPOSURE SHALL ALSO
 APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF EXPOSURE
 C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND
 DIRECTION.
  
 1J)(4) SINCE THE EXPOSURE "C" HAS ADJUSTMENT FACTOR
 PLEASE REVIEW PRESSURES. PROVIDE THE MEAN ROOF HEIGHT.
 A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * SHALL
 BE DETERMINED FROM TABLE 1609.6.2.1(4) THEDESIGNER OF
 RECORD IS APPERANTLY LOOKING FOR END ZONE CONDITIONS
 "WORST CASE" WITH PRESSURES OF -60.88 (A-1)
 THE SUBMITTED PRODUCT APPROVAL FOR THE FRONT DOOR ARE
 LOW AT +/-55 PSF.
  
 1K) SECOND REQUEST, WILL NEED TO BE RE-REVIEWED FOR
 EXPOSURE "C" FACTORS. NOTE NO PRODUCT APPROVALS WERE
 SUBMITTED.
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 1) EXTERIOR DOORS FRONT ENTRY
 2) EXERIOR SIDE DOORS- MISSING
  
 1L)2ND REQUEST. 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 1M) SECOND REQUEST, NEW EXTERIOR OPENINGS PLEASE
 PROVIDE DETAILS ON THE MWFRS CONTINIOUS LOAD PATH. WITH
 REQUEST IS NOW FOR THE NEW EXIT RECESS FOR BANQUET
 HALL # 3& 4.
  
 1N)COMPLIED.
  
 1O) SECOND REQUEST, PLEASE PROVIDE MANUFACTURERS
 DETAILS ON THE FOLDING PARTITION AS TO INSTALATION,
 106.1.2 ADDITIONAL INFORMATION REQUIRED. IT IS NOT
 KNOWN IF THESE LOADS WILL BE IMPOSED ONTO THE ROOF
 CEILING ASSEMBLY OR NOT? AND WHAT THESE LOADS MAY BE,
 THIS ITEM CAN BE A BUILDING PROVISO: AND BE SUBMITTED
 AFTER THTE PERMIT ISSUANCE ONCE REVIEWED BY THE DESIGN
 PROFESSIONAL.
  
 1P) COMPLIED.
  
 1R) COMPLIED.
  
 1S) COMPLIED.
  
 2) COMPLIED.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  