Plan Review Notes
Plan Review Notes For Permit 10070389
Permit Number 10070389
Review Stop P
Sequence Number 1
Notes
Date Text
2010-07-27 15:23:30FBC PLUNBING 2007 REVIEW #1
 DENIED:
  
 1. IF FROM BUILDING TOTAL OCCUPANTS IS 614 THEN
 REQUIRED WATER CLOSETS FOR WOMEN WOULD BE 5.
 PLUMBING TABLE 403.1
  
 2. ONE SERVICE SINK WILL BE REQUIRED TABLE 403.1
  
 3. ONE UNISEX TOILET WOULD BE REQUIRED
 E. IN ASSEMBLY AND MERCANTILE OCCUPANCIES, A UNISEX
 TOILET ROOM, IN ACCORDANCE WITH SECTION 403.7, SHALL BE
 PROVIDED WHERE AN AGGREGATE OF SIX OR MORE MALE AND
 FEMALE WATER CLOSETS ARE REQUIRED. IN BUILDINGS OF
 MIXED OCCUPANCY, ONLY THOSE WATER CLOSETS REQUIRED FOR
 THE ASSEMBLY OR MERCANTILE OCCUPANCY SHALL BE USED TO
 DETERMINE THE UNISEX TOILET ROOM REQUIREMENT.
  
 4. FBC 2007 11-4.17 ADA STALL SHALL COMPLY WITH FIGURE
 30(E)
  
 5. A DOMESTIC WATER RISER DIAGRAM IS REQUIRED.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 6. ALTHOUGH THE FIXTURE COUNT MAY CHANGE, THE CURCUIT
 VENT IN THE SANITARY RISER WILL REQUIRE A DRY VENT
 BETWEEN THE LAST TWO WATER CLOSETS FBC PLUMBING 911.2
  
 7. 4" PIPE IS REQUIRED UP TO THE FIRST ADA WATER CLOSET
 IN DRAWING.
 PLUMBING TABLE 710.1 (2)
  
 8. THE FLOOR DRAINS IN THE RESTROOMS REQUIRE TRAP
 PRIMERS.
  
 REVIEW BY LARRY WAGNER