2010-07-21 10:36:29 | BUILDING PLAN REVIEW |
| PERMIT: 08010251/ REV 10070389 |
| ADD: 2223 PALM BEACH LAKES # 101 |
| CONT: ADELFOS CONSTRUCTION |
| TEL: (561)662-2455 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) 2007 EXISTING BUILDING CODE. 912.1.4 ACCESSIBILITY. |
| ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH SECTION 912.8. 912.8 |
| ACCESSIBILITY. EXISTING BUILDINGS OR PORTIONS THEREOF |
| THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| 11-4.1.6(1)(D) NO ALTERATION OF AN EXISTING ELEMENT, |
| SPACE, OR AREA OF A BUILDING OR FACILITY SHALL IMPOSE A |
| REQUIREMENT FOR GREATER ACCESSIBILITY THAN THAT WHICH |
| WOULD BE REQUIRED FOR NEW CONSTRUCTION. |
| |
| 1A) PLEASE PROVIDE A SITE PLAN WITH THE NEW EGRESS |
| DOORS AT SIDE OF BUILDING INDICATING THE ACCESSIBLE |
| PATH TO THE PUBLIC WAY. 11-4.1.3(8)(A)(II) ACCESSIBLE |
| ENTRANCES MUST BE PROVIDED IN A NUMBER AT LEAST |
| EQUIVALENT TO THE NUMBER OF EXITS REQUIRED BY THE |
| APPLICABLE BUILDING/FIRE CODES. |
| |
| 1B) PLANS INDICATE A CHANGE IN OCCUPANCY,A A-3 |
| OCCUPANCY WITH 4292 SQ FT OF A-3 OCCUPANCY WITH UNFIXED |
| SEATING. TABLE 1004.1.1 INDICATES 7 SQ FT PER OCCUPANT |
| PROVIDING AN OCCUPANT LOAD OF 614 PLEASE CORRECT |
| OCCUPANCY DATA TABULATION. |
| |
| 1C) PLEASE UPDATE THE OCCUPANCY DATA TABULATION FOR |
| EACH OF THE ASSEMBLY ROOMS USING 7 SQ FT/ OCCUPANT FOR |
| UNFIXED SEATING USAGE. TABLE 1004.1.1. |
| |
| 1D) PLEASE REVIEW NOTE ON A-2 FOR A MINIMUM OF 8 INCHES |
| BETWEEN THE ACCORDIAN DOOR AND NEW DOOR. SEE ROOM 107 |
| AND SECTION 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT |
| ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN |
| IN FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE |
| REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL. |
| |
| 1E) SHEET A-2 AND E-1 BOTH INDICATE ROOM 106 TO BE A |
| KITCHEN, KITCHETTE. PLEASE REVIEW 1014.2 EXCEPTION# 1 |
| NO EGRESS THROUGH A KITCHEN. |
| |
| 1F) SHEET A-2 INDICATES AN EXIT CORRIDOR # 102 WITH |
| UNRATED CORRIDOR WALLS, PLEASE REVIEW FBC-B TABLE |
| 1017.1 WHICH REQUIRES RATED WALL. |
| |
| 1G) SHEET A-2 CORRIDOR 102 REQUIRES 1 HR RATED WALLS |
| PLEASE REVIEW FBC-B TABLE 715.4 FOR OPENING |
| PROTECTIVES. |
| |
| 1H) PLEASE PROVIDE ON THE SITE PLAN, THE DISTANCE FROM |
| THE PROPERTY LINE TO THE NEW EXTERIOR DOOR. TABLE |
| 704.8. |
| |
| 1I) THE BACK EXIT PLESE INDICATE BACK EXIT CONDITIONS, |
| IS THIS AN ACCESSIBLE EGRESS? 11-4.1.6(1)(D). & |
| EXISTING BUILDING CODE TABLE 912.4 |
| |
| |
| 1J) PLANS ALSO INDICATE ON A-2 A NEW STOREFRONT DOOR |
| AND WINDOW SYSTEM, PLEASE PROVIDE WIND DESIGN CRITERIA: |
| |
| 1609.6.2 WIND DESIGN PROCEDURES |
| 1J)(1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| |
| 1J)(2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| ACCORDANCE WITH SECTION1609.5. |
| |
| 1J)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4. |
| |
| 1J)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| |
| 1K) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES, |
| 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| 1) EXTERIOR DOORS |
| 2) DOORS |
| |
| 1L) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 1M) NEW EXTERIOR OPENINGS PLEASE PROVIDE DETAILS ON THE |
| MWFRS CONTINIOUS LOAD PATH. |
| |
| 1N) A-2 INDICATES NEW STOREFRONT SYSTEM AND DECREASING |
| THE STOREFRONT OPENING BY APPROXIMATELY 12 LINIEAL FEET |
| WITH NO STRUCTURAL INFORMATION ON THE EXTERIOR WALL |
| SYSTEM.MWFRS |
| CONTINIOUS LOAD PATH. |
| |
| 1O) PLEASE PROVIDE MANUFACTURERS DETAILS ON THE FOLDING |
| PARTITION AS TO INSTALATION, 106.1.2 ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| 1P) SHEET A-2 FAILS TO INDICATE COMPLIANCE WITH FBC-B |
| 906.1. |
| |
| 1R) PLEASE PROVIDE COMPLIANCE WITH INTERIOR FINISHES |
| FBC-B 803.1 & TABLE 803.5. |
| |
| 1S) MISSING DETAILS ON THE KITCHEN SINK: |
| SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED |
| WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH |
| FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| SINK |
| |
| 2) THE A SHEETS NOR E-1 INDICATE COMPLIANCE WITH THE |
| 2007 EXISTING BUILDING CODE 912.2.2 FIRE ALARM SYSTEMS |
| & 2007 FBC-B 907.2.1 ALSO REVIE EXCEPTION. |
| |
| 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| NOTICE. |
| |
| OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| - 5:00 PM. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |