Plan Review Notes For Permit 10070304 |
Permit Number |
10070304 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-07-14 14:16:26 | RESIDENTIAL (R2) ALTERATION LEVEL 1 BUILDING REVIEW | | CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- CERTIFIED BUILDING CONTRACTOR (CBC) IS NOT ALLOWED | | TO DO THE REPLACEMENT OF SLIDING GLASS DOORS. SEE | | CHAPTER 489.105 OF FLORIDA STATUTES FOR SCOPE OF WORK | | ALLOWED TO BE PERFORMED BY THE CBC. NEED GENERAL | | CONTRACTOR OR CONTRACTOR WITH SPECIALTY LICENSE TO DO | | THIS JOB. | | | | 2- PROVIDE SIGNED AND SEALED CALCULATIONS FOR THE | | DESIGN PRESSURES AS REQUIRED TO SHOW COMPLIANCE WITH | | THE DESIGN PRESSURES OF SEC. 1609 OF 2007 FBC. | | | | 3- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION | | IS TOO LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. NEED TO | | UPDATE VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | ENGINEERING AND CONTRACTOR'S OVERHEAD AND PROFIT. | | REVISE AS REQUIRED. | | | | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED | | BY 713.13 FLORIDA STATUTES. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER. | | (561)805-6712 |
|