2010-07-27 14:38:05 | 6501 NORTH JOG ROAD | | PERMIT NUMBER 10070303 | | "INSTALL FIRE ALARM SYSTEM" | | | | 1. WRONG LIFE SAFETY CODE REFERENCED ON PAGE FS-1. | | SHOULD READ 2006 EDITION NOT 2004 EDITION. SAME PROBLEM | | EXISTS ON PAGE FS-3. | | | | 2. PLANS ILLUSTRATE FIRE ALARM AND FM200 FIRE | | SUPPRESSION EQUIPMENT. PERMIT APPLICATION ONLY REFLECTS | | INSTALLATION OF FIRE ALARM SYSTEM. | | | | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR THE | | INSTALLATION OF THE FM200 FIRE SUPPRESSION SYSTEM. | | | | 4. PLEASE ILLUSTATRATE WIRES TO THE INITIATING AND | | SIGNALING APPLIANCES SHOWN ON THE FLOOR. | | | | 5. PLEASE REMIT A COPY OF THE CONTRACT AS THE VALUE | | APPEARS LOW. IS THE VALUE REFLECTED ON THE PERMIT THAT | | FOR THE FIRE ALARM AND THE FM200 SYSTEM? THE VALUE OF | | THE PERMIT SHOULD INCLUDE LABOR AND MATERIALS. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|