Plan Review Notes
Plan Review Notes For Permit 10070277
Permit Number 10070277
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-07-23 13:13:31*****DENIED*****
  
 1) PROVIDE CORRECT ADDRESS; 400 NORTH FLAGLER DRIVE NOT
 400 SOUTH FLAGLER DRIVE
 2) HVAC DUCT DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM CONDITION.
 3) PROVIDE SMOKE ALARMS OUTSIDE EVERY SLEEPING AREA.
 4) PROVIDE ANNUNCIATOR PANEL
 5) DEVICE ADDRESSES NOT GIVEN
 6) PLEASE PROVIDE WHAT VOICE EVACUATION MESSAGE WILL
 SAY
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730
  