Plan Review Notes For Permit 10070269 |
Permit Number |
10070269 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-07-14 19:36:59 | ****PROVISO**** | | ****REVISION REQUIRED**** | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | PROVIDE A REVISED INSTALLATION SCHEDULE. WALL MOUNT, | | SOLID SET, 3" EDGE DISTANCE REQUIRES A .78 FACTOR | | APPLIED TO ANCHOR SPACING. SOMEONE CIRCLED THIS ON THE | | PRODUCT APPROVAL BUT DID NOT APPLY THE FACTOR. ANCHOR | | SPACING PROPOSED ***DOES NOT*** COMPLY WITH DESIGN | | PRESSURES. | | | | FOR INSTANCE: OPENING 1, 10" ANCHOR SPACING TO BE | | MULTIPLIED BY .78 FACTOR = 7.8". | | | | |
|