Plan Review Notes For Permit 10070232 |
Permit Number |
10070232 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-07-14 08:28:33 | ***PROVISO**** | | ***REVISION REQUIRED BEFORE FIRST INSPECTION*** | | ***ISSUED AT CONTRACTOR'S RISK**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | PROVIDE A STRUCTURAL DETAIL FOR BLOCK INFILL WHICH | | INCLUDES INFORMATION REGARDING HOW THE INFILL WILL BE | | CONTINUOUS WITH THE REMAINDER OF THE WALL IN ORDER TO | | RESIST LOADS (FOR EXAMPLE, SPECIFY STEEL REINFORCEMENT | | AND EMBEDMENT INTO EXISTING) | | | | PLAN SHOWS AN A/C OPENING AT THE BOTTOM OF THE OVERALL | | OPENING. HOW WILL THE BLOCK PROPOSED ABOVE THIS OPENING | | BE SUPPORTED? PROVIDE A DETAIL | | | | | | | | | | |
|