Notes
Date Text
2010-07-14 08:28:33***PROVISO****
 ***REVISION REQUIRED BEFORE FIRST INSPECTION***
 ***ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 PROVIDE A STRUCTURAL DETAIL FOR BLOCK INFILL WHICH
 INCLUDES INFORMATION REGARDING HOW THE INFILL WILL BE
 CONTINUOUS WITH THE REMAINDER OF THE WALL IN ORDER TO
 RESIST LOADS (FOR EXAMPLE, SPECIFY STEEL REINFORCEMENT
 AND EMBEDMENT INTO EXISTING)
  
 PLAN SHOWS AN A/C OPENING AT THE BOTTOM OF THE OVERALL
 OPENING. HOW WILL THE BLOCK PROPOSED ABOVE THIS OPENING
 BE SUPPORTED? PROVIDE A DETAIL
  
  
  
  
  