Plan Review Notes
Plan Review Notes For Permit 10070193
Permit Number 10070193
Review Stop M
Sequence Number 2
Notes
Date Text
2010-08-13 13:06:00****CORRECTIONS****
 ****PLAN REVIEW IN PROGRESS****
  
 1. PREVIOUS LIST REQUESTED THAT PLAN SHOW DRYER EXHAUST
 DUCT AND DISCHARGE LOCATION IN ACCORDANCE WITH FBC
 M504.1 AND 504.6.2. MANUFACTURER'S INSTRUCTIONS NOT
 PROVIDED AND EXHAUST DETAIL NOT PROVIDED. DISTANCE FROM
 DRYER TO DISCHARGE NOT SHOWN ON PLAN. DUCT DETAIL NOT
 PROVIDED, DUCTWORK APPEARS TO BE SHOWN IN WALL BUT
 ISN'T THIS A FIRE RATED TENANT SEPARATION WALL?
  
 2. COMMENT FROM PREVIOUS LIST, SHOW HOW REQUIRED
 VENTILATION RATES FOR THIS USE ARE TO BE ACHIEVED IN
 ACCORDANCE WITH FBC EB 901.2 AND FBC M403.3. SEE TABLE
 FBC M403.1, ALSO FOOTNOTE (B) AND (I).
  
 3. SEE FBC501.2.1, PROVIDE A SITE PLAN SHOWING DISTANCE
 BETWEEN INTAKES AND OPENINGS.
  
 4. PROVIDE A DETAIL SHOWING HOW OTHER EXHAUST DUCTWORK
 IS TO BE INSTALLED.
  
 5. THE PLAN IS TO BE PREPARED BY A PROFESSIONAL
 LICENSED FOR DESIGN OF MECHANICAL SYSTEMS.
  
  
  
  
  