Plan Review Notes For Permit 10070193 |
Permit Number |
10070193 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-08-13 13:06:00 | ****CORRECTIONS**** | | ****PLAN REVIEW IN PROGRESS**** | | | | 1. PREVIOUS LIST REQUESTED THAT PLAN SHOW DRYER EXHAUST | | DUCT AND DISCHARGE LOCATION IN ACCORDANCE WITH FBC | | M504.1 AND 504.6.2. MANUFACTURER'S INSTRUCTIONS NOT | | PROVIDED AND EXHAUST DETAIL NOT PROVIDED. DISTANCE FROM | | DRYER TO DISCHARGE NOT SHOWN ON PLAN. DUCT DETAIL NOT | | PROVIDED, DUCTWORK APPEARS TO BE SHOWN IN WALL BUT | | ISN'T THIS A FIRE RATED TENANT SEPARATION WALL? | | | | 2. COMMENT FROM PREVIOUS LIST, SHOW HOW REQUIRED | | VENTILATION RATES FOR THIS USE ARE TO BE ACHIEVED IN | | ACCORDANCE WITH FBC EB 901.2 AND FBC M403.3. SEE TABLE | | FBC M403.1, ALSO FOOTNOTE (B) AND (I). | | | | 3. SEE FBC501.2.1, PROVIDE A SITE PLAN SHOWING DISTANCE | | BETWEEN INTAKES AND OPENINGS. | | | | 4. PROVIDE A DETAIL SHOWING HOW OTHER EXHAUST DUCTWORK | | IS TO BE INSTALLED. | | | | 5. THE PLAN IS TO BE PREPARED BY A PROFESSIONAL | | LICENSED FOR DESIGN OF MECHANICAL SYSTEMS. | | | | | | | | | | |
|