2010-07-13 10:25:19REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLAN SHOWS NEW DRYER BEING INSTALLED. SHOW DRYER
 EXHAUST DUCT AND DISCHARGE LOCATION IN ACCORDANCE WITH
 FBC-M 504.1 AND 504.6.2.
  
 2. NO INFORMATION ON PLANS REGARDING VENTILATION. SHOW
 HOW REQUIRED VENTILATION RATES FOR THIS USE ARE TO BE
 ACHIEVED IN ACCORDANCE WITH FBC-EB 901.2 AND FBC-M
 403.3.
  
 A THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME.
  