2010-08-04 10:30:13BUILDING #6 - 8 UNIT TOWNHOUSES
  
 DENIED BY MECHANICAL
  
 1) THE RETURN AIR TRANSFER DUCT FROM THE MASTER BEDROOM
 SUITE IS UNDER SIZED. FBC R M1602.4 REQUIRES THE
 TRANSFER DUCT TO BE 1.5 TIMES THE SUPPLY, THEREFORE A
 14" DUCT IS REQUIRED.
 PLEASE CORRECT.
  
 2) THE EQUIPMENT MODEL NUMBERS ON THE PLANS AND THE
 SIZING CALCS. DO NOT MATCH FOR THE END UNITS. PLEASE
 CORRECT.
  
 3) THE CU MOUNTING DETAIL ON THE MECHANICAL PLANS
 REFERENCES THE 2004 FBC AND ASCE 02. PLEASE UPDATE TO
 2007 FBC AND ASCE7-05 AND CORRECT THE SECTIONS THAT ARE
 LISTED.
  