2010-08-04 10:30:13 | BUILDING #6 - 8 UNIT TOWNHOUSES | | | | DENIED BY MECHANICAL | | | | 1) THE RETURN AIR TRANSFER DUCT FROM THE MASTER BEDROOM | | SUITE IS UNDER SIZED. FBC R M1602.4 REQUIRES THE | | TRANSFER DUCT TO BE 1.5 TIMES THE SUPPLY, THEREFORE A | | 14" DUCT IS REQUIRED. | | PLEASE CORRECT. | | | | 2) THE EQUIPMENT MODEL NUMBERS ON THE PLANS AND THE | | SIZING CALCS. DO NOT MATCH FOR THE END UNITS. PLEASE | | CORRECT. | | | | 3) THE CU MOUNTING DETAIL ON THE MECHANICAL PLANS | | REFERENCES THE 2004 FBC AND ASCE 02. PLEASE UPDATE TO | | 2007 FBC AND ASCE7-05 AND CORRECT THE SECTIONS THAT ARE | | LISTED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|