Plan Review Notes
Plan Review Notes For Permit 10070171
Permit Number 10070171
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-07-28 11:10:16OAKTON PRESERVE
 PERMIT NUMBER 10070137
 LOTS35,36,37,38,39,40,41, AND 42
  
 1. PER FLORIDA STATUE 553.885, THE CARBON MONOXIDE
 DETECTORS SHOWN ON THE SECOND FLOORS MUST BE INSTALLED
 WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES.
  
 2. PER FLORIDA STATUE 633.027 "THE OWNER OF ANY
 COMMERCIAL OR INDUSTRIAL STRUCTURE, OR ANY MULT-UNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE, THAT USES
 LIGHT-FRAME TRUSS CONSTRUCTION SHALL MARK THE STRUCTURE
 WITH A SIGN APPROVED BY THE STATE FIRE MARSHAL IN A
 MANNER SUFFICIENT TO WARN PERSONS CONDUCTING FIRE
 CONTROL AND OTHER EMERGENCY OPERATIONS OF THE EXISTENCE
 OF LIGHT FRAME TRUSS TYPE CONSTRUCTION IN THE
 STRUCTURE".
  
 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 4. THE EGRESS WINDOW FOR BEDROOM 2 NOT IDENTIFIED ON
 PAGE TU-2.1.
  
 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS IN EACH UNIT.
  
 6. UNITS 35-36 ON PAGE A-3.1. HAVE NO PREMISES
 IDENTIFICATION.
  
 7. PORTABLE FIRE EXTINGUISHERS NOT SHOWN?
  
 8. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT
 LEAST 10 FEET FROM AIR CONDITIONER DIFUSERS.
  
 9. PROVIDE DETAILS ON FIRE RETARDANT COATINGS DESCRIBED
 ON PAGES A-4.1 AND A-4.2.
  
 10. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  