2010-07-28 11:10:16 | OAKTON PRESERVE |
| PERMIT NUMBER 10070137 |
| LOTS35,36,37,38,39,40,41, AND 42 |
| |
| 1. PER FLORIDA STATUE 553.885, THE CARBON MONOXIDE |
| DETECTORS SHOWN ON THE SECOND FLOORS MUST BE INSTALLED |
| WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. |
| |
| 2. PER FLORIDA STATUE 633.027 "THE OWNER OF ANY |
| COMMERCIAL OR INDUSTRIAL STRUCTURE, OR ANY MULT-UNIT |
| RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE, THAT USES |
| LIGHT-FRAME TRUSS CONSTRUCTION SHALL MARK THE STRUCTURE |
| WITH A SIGN APPROVED BY THE STATE FIRE MARSHAL IN A |
| MANNER SUFFICIENT TO WARN PERSONS CONDUCTING FIRE |
| CONTROL AND OTHER EMERGENCY OPERATIONS OF THE EXISTENCE |
| OF LIGHT FRAME TRUSS TYPE CONSTRUCTION IN THE |
| STRUCTURE". |
| |
| 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| WITH NFPA 241. |
| |
| 4. THE EGRESS WINDOW FOR BEDROOM 2 NOT IDENTIFIED ON |
| PAGE TU-2.1. |
| |
| 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATION FOR |
| WALLS AND CEILINGS IN EACH UNIT. |
| |
| 6. UNITS 35-36 ON PAGE A-3.1. HAVE NO PREMISES |
| IDENTIFICATION. |
| |
| 7. PORTABLE FIRE EXTINGUISHERS NOT SHOWN? |
| |
| 8. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT |
| LEAST 10 FEET FROM AIR CONDITIONER DIFUSERS. |
| |
| 9. PROVIDE DETAILS ON FIRE RETARDANT COATINGS DESCRIBED |
| ON PAGES A-4.1 AND A-4.2. |
| |
| 10. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| FOR HANDRAILS AND GUARDRAILS. |
| |
| |
| DENIED |
| |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |
| |