2010-08-04 11:24:31 | REVISION REQUIRED | | | | 1) THE PRODUCT APPROVALS SUBMITTED FOR THE 8' X 16' | | GARAGE DOOR NEEDS TO BE UPDATED TO THE 2007 CODE | | EDITION. THE DESIGN PRESSURES FOR THE OAK SUMMIT MODEL | | DO NOT MEET THE REQUIRED OPENING PRESSURES FOR EXPOSURE | | C INDICATED ON THE PLANS. | | | | 2) SUBMIT THE PRODUCT APPROVAL FOR THE POLYSTICK | | UNDERLAYMENT HAS BEEN SUPERSEDED. SUBMIT THE CURRENT | | PRODUCT APPROVAL WITH NOA NO. 09-0806.07. | | | | NOTE: DESIGNER OF RECORD IS REQUIRED TO REVIEW AND | | APPROVE PRODUCT APPROVALS IN WRITING. |
|