Plan Review Notes For Permit 10070135
Permit Number 10070135
Review Stop M
Sequence Number 2
Notes
Date Text
2010-11-16 10:28:26PASS PROVISO
 PLEASE REFER TO SECTION 13-409.AB.3.3 FLA.ENERGY CODE
 2007 SHUTOFF DAMPER CONTROLS. BOTH OUTDOOR AIR SUPPLY
 AND EXHAUST SYSTEMS SHALL BE EQUIPPED WITH MOTORIZED
 DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS
 OR SPACE SERVED ARE NOT IN USE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732