Plan Review Notes For Permit 10070135 |
Permit Number |
10070135 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-07-29 09:40:48 | 425-25TH STREET | | PERMIT NUMBER 10070135 | | ALTERATIONS AND REPAIR | | | | | | 1. NOTE ON PAGE A-1 REFERENCES "EXISTING HOUSE". PLANS | | ARE FOR A COMMERCIAL BUILDING. | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE | | RELOCATION OF THE EXISTING FIRE SUPPRESSION SYSTEM. | | KITCHEN FIRE SUPPRESSION SYSTEM SHALL MEET THE UL 300 | | STANDARD FOR KITCHEN FIRE SUPPRESSION SYSTEMS. | | | | 3. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE | | NATIONAL ELECTRIC CODE. | | | | 4. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | APPROVED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|