Plan Review Notes
Plan Review Notes For Permit 10070097
Permit Number 10070097
Review Stop B
Sequence Number 1
Notes
Date Text
2010-07-14 17:46:29****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. INSTALLATION SCHEDULE STATES THAT CONNECTION TYPE
 PROPOSED IS C1, BUT THE PRODUCT APPROVAL SUBMITTED DOES
 NOT HAVE CONNECTION MOUNTING TYPES C1 THROUGH C5 (AS IS
 TYPICAL ON MANY PRODUCT APPROVALS). THIS PRODUCT
 APPROVAL IMPLEMENTS A NAMING CONVENTION OF 1 (TOP)
 THROUGH 5 (BOTTOM). PLEASE REVISE INSTALLATION SCHEDULE
 TO CORRELATE WITH THE PRODUCT APPROVAL. SEE ANCHOR
 CHARTS ON PAGE 7.
  
 2. SPECIFIC ANCHOR TYPE IS TO CORRELATE WITH THE
 PRODUCT APPROVAL. PANELMATES ARE PROPOSED, BUT I WAS
 UNABLE TO LOCATE THIS ANCHOR TYPE ON THE PRODUCT
 APPROVAL (HAS TWO DIFFERENT TAPCONS, SOLID SET). IF AN
 ANCHOR IS PROPOSED WHICH IS NOT INCLUDED IN THE PRODUCT
 APPROVAL, ENGINEERING REQUIRED. SEE PAGE 7 OF PRODUCT
 APPROVAL.
  
 3. A 2.5" EDGE DISTANCE IS PROPOSED. PLEASE SEE SHEET
 7; A FACTOR OF .71 OR .50 IS TO BE APPLIED TO 2.5"
 ANCHOR SPACING.
  
 4. SPANS DO NOT APPEAR TO BE CORRECT. FOR INSTANCE,
 OPENING 15, 34" WIDE OPENING WITH A HORIZONTAL
 INSTALLATION, 2.5" EDGE DISTANCE, SHOULD HAVE A SPAN OF
 39" BUT 44" IS STATED. SOME OPENINGS HAVE A DIFFERENCE
 OF 20" BETWEEN SPAN AND OPENING SIZE. FOR PANELS, SPANS
 SHOULD BE THE DISTANCE BETWEEN ANCHORS, TYPICALLY
 OPENING SIZE PLUS EDGE DISTANCE ON EACH SIDE OF PANEL.
  
 ANOTHER EXAMPLE: OPENING 18, 58" WITH 2.5" EDGE
 DISTANCE, SPAN SHOULD BE 63", BUT 62" IS SPECIFIED.
 PLEASE CHECK ALL.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU NEED ASSISTANCE.
  