Plan Review Notes For Permit 10070075 |
Permit Number |
10070075 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-07-06 12:10:55 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- SPECIFY WHICH APPROVED ASSEMBLY OF NOA 08-0227.07 | | SUBMITTED IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE | | WITH THE DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA | | RESIDENTIAL CODE. | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. THIS CALCULATIONS ARE REQUIRED TO MEET THE | | DESIGN PRESSURES OF SEC. R301. DESIGN PROFESSIONAL | | DOING THE RAS 117 CALCULATIONS TO TAKE INTO | | CONSIDERATION THAT ACCORDING TO THE 2009 REVISIONS THIS | | BUILDING IS IN EXPOSURE "C". | | | | ***NOTE: APPROVED ASEMBLIES THAT ARE LIMITED BY GENERAL | | LIMITATION #9 CAN'T BE USED IN THIS BUILDING BECAUSE | | THIS LIMITATION DOESN'T ALLOW NAIL ENHANCING. SEE LAST | | PAGE OF NOA SUBMITTED. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | | | |
|