2010-07-12 16:49:37 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. MASTER PERMIT TO BE ISSUED PRIOR TO ISSUANCE OF SITE | | PERMITS. | | | | 2. PLEASE PROVIDE A SOILS INVESTIGATION REPORT, 2000 | | PSF BEARING MINIMUM | | | | 3. PROPOSED FINISHED FLOOR ELEVATION FBC403.1.7.3. | | | | 4. PROVIDE THE STAIR AND HANDRAIL/GUARDRAIL DETAIL (MAY | | BE UNDER SEPARATE PERMIT). SHOW DISTANCE OF STAIR TO | | PROPERTY LINE, FBC R302.1, FBC TABLE R302.1. | | | | 5. SEPARATE PERMITS FOR ELECTRIC HOOKUP, PLUMBING | | HOOKUP, MECHANICAL, IMPACT PROTECTION, ROOF | | | | 6. SITE SPECIFIC ENERGY CALCS REQUIRED, FBC11-6. | | | | 9. IMPACT FEE ASSESSMENT REQUIRED, 561-233-5025. PLANS | | ARE TO BE STAMPED AND THE RECEIPT ATTACHED TO | | APPLICATION. | | | | 10. PROVIDE OVERALL DIMENSIONS OF PROPOSED STRUCTURE ON | | THE SITE PLAN. THE STRUCTURAL PLAN SHOWS THE MASTER AS | | 62' DEEP, BUT 62'+20.5' (FRONT) + 61.5' (REAR) ADDS UP | | TO 144', BUT THE SITE PLAN SHOWS A 133' LOT DEPTH. | | WIDTH ALSO DOES NOT ADD UP TO EQUAL SETBACKS PLUS | | STRUCTURE. | | | | 11. PLEASE HAVE SURVEYOR CONTACT ME AS I WAS UNABLE TO | | LOCATE THE LOT DEPTH ON THE SURVEY, OR REVISE SURVEY TO | | INCLUDE THE INFORMATION. FS472.027. | | | | | | | | |
|