Plan Review Notes
Plan Review Notes For Permit 10070052
Permit Number 10070052
Review Stop B
Sequence Number 1
Notes
Date Text
2010-07-12 16:49:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. MASTER PERMIT TO BE ISSUED PRIOR TO ISSUANCE OF SITE
 PERMITS.
  
 2. PLEASE PROVIDE A SOILS INVESTIGATION REPORT, 2000
 PSF BEARING MINIMUM
  
 3. PROPOSED FINISHED FLOOR ELEVATION FBC403.1.7.3.
  
 4. PROVIDE THE STAIR AND HANDRAIL/GUARDRAIL DETAIL (MAY
 BE UNDER SEPARATE PERMIT). SHOW DISTANCE OF STAIR TO
 PROPERTY LINE, FBC R302.1, FBC TABLE R302.1.
  
 5. SEPARATE PERMITS FOR ELECTRIC HOOKUP, PLUMBING
 HOOKUP, MECHANICAL, IMPACT PROTECTION, ROOF
  
 6. SITE SPECIFIC ENERGY CALCS REQUIRED, FBC11-6.
  
 9. IMPACT FEE ASSESSMENT REQUIRED, 561-233-5025. PLANS
 ARE TO BE STAMPED AND THE RECEIPT ATTACHED TO
 APPLICATION.
  
 10. PROVIDE OVERALL DIMENSIONS OF PROPOSED STRUCTURE ON
 THE SITE PLAN. THE STRUCTURAL PLAN SHOWS THE MASTER AS
 62' DEEP, BUT 62'+20.5' (FRONT) + 61.5' (REAR) ADDS UP
 TO 144', BUT THE SITE PLAN SHOWS A 133' LOT DEPTH.
 WIDTH ALSO DOES NOT ADD UP TO EQUAL SETBACKS PLUS
 STRUCTURE.
  
 11. PLEASE HAVE SURVEYOR CONTACT ME AS I WAS UNABLE TO
 LOCATE THE LOT DEPTH ON THE SURVEY, OR REVISE SURVEY TO
 INCLUDE THE INFORMATION. FS472.027.
  
  
  
  