2010-07-15 14:07:28BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PERMIT APPLICATION SUBMITTED IS FOR MECHANICAL AND
 ELECTRICAL PERMITS ONLY. QUALIFIED CONTRACTOR NEEDS TO
 APPLY FOR THE BUILDING PERMIT FOR THE CONSTRUCTION OF
 THE COUNTERTOP BY THE TAKE OUT AREA. UPDATE VALUATION
 TO INCLUDE THE SCOPE OF WORK TO BE DONE BY THE GENERAL
 CONTRACTOR AND THE DESIGN PROFESSIONAL FEES AS REQUIRED
 BY SEC. 108.3 OF CITY AMENDMENTS TO FBC.
  
 2- DRAWING C1:
 A) REVISE CODE ANALYSIS INFORMATION.
 (1) OCCUPANCY CLASSIFICATION IS NOT BUSINESS. SEE
 CHAPTER 3 OF 2007 FBC AND REVISE AS REQUIRED.
 (2) REVISE CONSTRUCTION TYPE. THIS BUILDING IS NOT
 TIMBER CONSTRUCTION. REVISE AS REQUIRED.
 (3) REVISE TOTAL OCCUPANT LOAD SPECIFIED TO INCLUDE THE
 EXISTING RETAIL AREA.. SEE TABLE 1004.1.1 AND REVISE AS
 REQUIRED.
  
 B) REVISE THE MINIMUM INTERIOR FINISH CLASSIFICATION
 TABLE AT THE BOTTOM OF THE GENERAL NOTES COLUMN ON THE
 LEFT BOTTOM OF THE PAGE TO MATCH SPECIFIED OCCUPANCY
 CLASSIFICATION. THIS IS NOT ASSEMBLY TYPE. COORDINATE
 WITH ITEM 2(A)(1) ABOVE.
  
 3- DRAWING A-1: A) SPECIFY ALL DIMENSIONS BY THE TAKE
 OUT COUNTER AREA TO VERIFY COMPLIANCE WITH THE
 ACCESSIBILITY REQUIREMENTS OF CHAPTER 11 OF 2007 FBC.
 SHOW THE WHEELCHAIR TURNING SPACE IN FRONT OF DISPLAY
 CABINET AND COUNTERTOP AREA AS REQUIRED BY SEC.
 11-4.2.3 OF 2007 FBC.
  
 B) WALL SHOWN BY EXISTING OFFICE IS NOT SHOWN ON THE
 WALL LEGEND. CLARIFY IF NEW WALL. CHECK WITH CHAPTER 11
 DOOR MANEUVERING REQUIREMENTS.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712