2010-07-07 15:02:551901 NORTH FLAGLER DRIVE
 TEMPLE ISRAEL
 PERMIT NUMBER 10060819
 FIRE SPRINKLER PLAN
  
 1. CONSTRUCTION DOCUMENT SHEET FP-2 LABELS STORAGE # 2
 -205 AND MECHANICAL # 2-291 AS ORDINARY HAZARD GROUP II
 AND A DENSITY .2 GPM PER SQUARE FOOT. PLEASE PROVIDE
 HYDRAULIC CALCULATIONS.
  
 2. STORAGE ROOM # 2-205 HAS A SPRINKLER IN THE NE
 CORNER THAT IS CONNECTED TO ANY PIPE.
  
 3. HYDRAULICALLY CALCULATED AREA IS LESS THAN 900
 SQUARE FEET.
  
 4. FLEXHEAD DETAIL IS DIFFICULT TO READ. PLEASE PROVIDE
 THE FOLLOWING INFORMATION ON THE DRAWING LENGTH OF
 FLEXIBLE DROP, RADIUS OF FLEXIBLE CONNECTION, AND
 MAXIMUM NUMBER OF BENDS.
  
  
 DENIED
  
  
 WESLEY JOLIN, FIRE PROTECTION ENGINEER
 BUREAU OF FIRE PREVENTION
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION