Plan Review Notes
Plan Review Notes For Permit 10060807
Permit Number 10060807
Review Stop B
Sequence Number 3
Notes
Date Text
2010-09-07 13:32:31****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE DOOR (GARAGE) PROPOSED HAS A DP LIMITATION OF
 31.9/-37.2, THIS DOES NOT COMPLY WITH 140MPH EXP C. SEE
 ASCE7-05. PROPOSE A PRODUCT WHICH COMPLIES WITH THE
 WIND REQUIREMENTS OF FBC CH. 16. NOT ADDRESSED, 3RD
 TIME.
  
 2. SCOPE OF WORK IS NOT CLEAR. ON THE FLOOR PLAN,
 PLEASE INDICATE WHICH OPENINGS ARE TO BE INSTALLED. THE
 PHOTOGRAPH PROVIDED WITH FIRST REVIEW SHOWS ONE
 STOREFRONT/DOOR, BUT THE FLOOR PLAN PROVIDED DOES NOT
 SHOW AN OPENING OF THIS TYPE. SOMEONE FROM CONTRACTOR'S
 OFFICE STATED THAT NO WINDOWS ARE TO BE INSTALLED; WHY
 WERE STOREFRONT PRODUCT APPROVALS SUBMITTED? SHE ALSO
 STATED THAT A WINDOW WILL BE INSTALLED OVER THE GARAGE
 DOOR, BUT OPERABLE WINDOW PRODUCT APPROVAL WAS NOT
 SUBMITTED. AS DISCUSSED, PLEASE HAVE QUALIFIER CONTACT
 ME TO SCHEDULE A MEETING IF HE NEEDS ASSISTANCE IN
 ADDRESSING THE COMMENTS.
  
  
  
  
  