Plan Review Notes For Permit 10060807 |
Permit Number |
10060807 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-08-04 19:44:28 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED. | | | | THE PRODUCT APPROVAL SUBMITTED FOR THE DOOR EXPIRED ON | | 3/5/09. PLEASE PROVIDE A CURRENT VALID PRODUCT | | APPROVAL. | | | | 2. COMMENT NOT ADDRESSED FROM PREVIOUS REVIEW, MEAN | | ROOF HEIGHT OF THE BUILDING SO THAT DESIGN PRESSURE | | REQUIREMENTS CAN BE DETERMINED, FBC1609. THE DOOR | | PROPOSED HAS A DP LIMITATION OF 31.9/-37.2, THIS DOES | | NOT COMPLY WITH 140MPH EXP C. SEE ASCE7-05. PROPOSE A | | PRODUCT WHICH COMPLIES WITH THE WIND REQUIREMENTS OF | | FBC CH. 16. | | | | | | | | |
|