2010-08-04 19:44:28****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED.
  
 THE PRODUCT APPROVAL SUBMITTED FOR THE DOOR EXPIRED ON
 3/5/09. PLEASE PROVIDE A CURRENT VALID PRODUCT
 APPROVAL.
  
 2. COMMENT NOT ADDRESSED FROM PREVIOUS REVIEW, MEAN
 ROOF HEIGHT OF THE BUILDING SO THAT DESIGN PRESSURE
 REQUIREMENTS CAN BE DETERMINED, FBC1609. THE DOOR
 PROPOSED HAS A DP LIMITATION OF 31.9/-37.2, THIS DOES
 NOT COMPLY WITH 140MPH EXP C. SEE ASCE7-05. PROPOSE A
 PRODUCT WHICH COMPLIES WITH THE WIND REQUIREMENTS OF
 FBC CH. 16.
  
  
  
  