Plan Review Notes For Permit 10060807 |
Permit Number |
10060807 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-07-06 10:32:49 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED: | | | | A. A COPY OF A TEST REPORT WAS PROIVDED FOR THE GARAGE | | DOOR. ENTIRE PRODUCT APPROVAL, INCLUDING COVER SHEET, | | REQUIRED. | | B. PRODUCT APPROVAL FOR A GLASS WALL SYSTEM WAS | | PROVIDED. SEE SHEET 1 OF 11, THIS NOA DOES NOT INCLUDE | | THE DOOR. THE DOOR HAS A SEPARATE NOA. | | | | 2. THE APPLICATION STATES THAT A 10X3" GARAGE DOOR IS | | PROPOSED. PROVIDE CORRECT SIZE FOR GARAGE DOOR AND MEAN | | ROOF HEIGHT OF THE BUILDING SO THAT DESIGN PRESSURE | | REQUIREMENTS CAN BE DETERMINED, FBC1609. THE DOOR | | PROPOSED HAS A DP LIMITATION OF 31.9/-37.2, NOT CLEAR | | WHETHER THIS COMPLIES WITH 140MPH EXP C. SEE FBC TABLE | | 1609.6(1) AND (2). | | | | | | | | |
|