2010-07-06 10:32:49****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED:
  
 A. A COPY OF A TEST REPORT WAS PROIVDED FOR THE GARAGE
 DOOR. ENTIRE PRODUCT APPROVAL, INCLUDING COVER SHEET,
 REQUIRED.
 B. PRODUCT APPROVAL FOR A GLASS WALL SYSTEM WAS
 PROVIDED. SEE SHEET 1 OF 11, THIS NOA DOES NOT INCLUDE
 THE DOOR. THE DOOR HAS A SEPARATE NOA.
  
 2. THE APPLICATION STATES THAT A 10X3" GARAGE DOOR IS
 PROPOSED. PROVIDE CORRECT SIZE FOR GARAGE DOOR AND MEAN
 ROOF HEIGHT OF THE BUILDING SO THAT DESIGN PRESSURE
 REQUIREMENTS CAN BE DETERMINED, FBC1609. THE DOOR
 PROPOSED HAS A DP LIMITATION OF 31.9/-37.2, NOT CLEAR
 WHETHER THIS COMPLIES WITH 140MPH EXP C. SEE FBC TABLE
 1609.6(1) AND (2).
  
  
  
  