Plan Review Notes
Plan Review Notes For Permit 10060706
Permit Number 10060706
Review Stop B
Sequence Number 2
Notes
Date Text
2010-06-28 09:05:07RE-ROOF BUILDING REVIEW SECOND CHECKLIST.
  
 1- ENGINEER TO CLARIFY RAS 117 CALCULATIONS SUBMITTED.
 SCOPE OF ACTIVITIES IDENTIFIES NAIL SPACING 9" O/C @
 LAPS & 4 ROWS 10" O.C., 6" O/C @ LAPS & 6 ROWS 6" O.C.,
 AND 4" O/C @ LAPS & 9 ROWS 4" O.C. PROVIDE SKETCH
 SHOWING HOW IS THIS PROPOSED NAIL ENHANCING GOING TO BE
 INSTALLED.
 ***NOTE: ENGINEER TO TAKE INTO CONSIDERATION THAT THE
 MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN 4"
 O.C. SEE SEC. 8.1 OF RAS 117 CALCULATIONS.
  
 2- ENGINEER TO PROVIDE THE ENGINEERING FIRM CERTIFICATE
 OF AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 61G-15-23.002(2) OF FLORIDA ADMINISTRATIVE CODE AND
 SEC. 471 OF FLORIDA STATUTE.
  