Plan Review Notes For Permit 10060663 |
Permit Number |
10060663 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-28 12:35:32 | *****DENIED***** | | | | 1) SOUTHWEST AREA OF GRILL #109 DOES NOT HAVE SPRINKLER | | COVERAGE. CLOSEST SPRINKLER IS LOCATED ON OPPOSITE SIDE | | OF WALL. | | | | 2) ROOM LABELED COMFORT #108 NEAR COLUMN INTERSECTION | | 10/G FEATURES A WALL WITH AN ELECTRICAL PANEL. THE | | SPRINKLER IS LOCATED 10'-0" FROM THE WALL. | | | | 3) ARCHITECTURAL CEILING DETAIL FOR COMFORT #108 INFERS | | CEILING DOES NOT ENCLOSE THE ENTIRE ROOM. VERIFY | | CEILING IS NOT OPEN TO STRUCTURE ABOVE FLOATING SLOPED | | CLOUDS. IF CEILING HAS OPENINGS, PROVIDE SPRINKLER | | PROTECTION ABOVE CEILING. | | | | 4) THE 11'-0" RECTANGULAR CEILING WITH AN OVAL INTERIOR | | CEILING OF 9'-1" AND 8'-0" ONLY PROVIDES SPRINKLER | | PROTECTION FOR THE 9'-1" CEILING. THE FLOOR AREA BELOW | | THE 11'-0" AND 8'-0" CEILINGS ARE UNPROTECTED. | | ADDITIONAL SPRINKLERS MAY REQUIRE A SEPARATE BRANCH | | LINE TO AVOID OVER TAXING THE EXISTING BRANCH LINES. | | | | 5) PROVIDE NOTE ON THE DRAWING STATING AREAS OF EXPOSED | | STRUCTURE ARE CONSIDERED OBSTRUCTED CONSTRUCTION OR | | UNOBSTRUCTED CONSTRUCTION. | | | | | | CAPT. MICHAEL A. WILLIAMS | | & WESLEY JOLIN | | FIRE PLAN REVIEW | | 561-805-6730 |
|