Plan Review Notes
Plan Review Notes For Permit 10060646
Permit Number 10060646
Review Stop M
Sequence Number 3
Notes
Date Text
2010-09-16 16:56:38PROVISO
  
 1) THE TRANSFER GRILLS SHALL USE 50 SQUARE INCHES OF
 GRILL AREA TO 100 CFM FOR SIZING THROUGH THE WALL
 TRANSFER GRILLS TO ACHIEVE PROPER RETURN AIR BALANCE AS
 REQUIRED BY FBC M1602.4.
  
 2) NO RETURN AIR SHALL BE TAKEN FROM THE UTILITY ROOM.
 THE RETURN AIR FROM THE HALL SHALL BE DUCTED DIRECTLY
 TO THE AIR HANDLER PER FBC R M1602.2 (4).