2010-09-16 16:56:38 | PROVISO | | | | 1) THE TRANSFER GRILLS SHALL USE 50 SQUARE INCHES OF | | GRILL AREA TO 100 CFM FOR SIZING THROUGH THE WALL | | TRANSFER GRILLS TO ACHIEVE PROPER RETURN AIR BALANCE AS | | REQUIRED BY FBC M1602.4. | | | | 2) NO RETURN AIR SHALL BE TAKEN FROM THE UTILITY ROOM. | | THE RETURN AIR FROM THE HALL SHALL BE DUCTED DIRECTLY | | TO THE AIR HANDLER PER FBC R M1602.2 (4). |
|