Plan Review Notes For Permit 10060646 |
Permit Number |
10060646 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-08-25 15:39:52 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR ROOF | | COVERING, HURRICANE CONNECTORS AND STRAPS, WINDOWS, | | STRUCTURAL MULLIONS AND IMPACT PROTECTION DEVICES AS | | REQUIRED BY DCA RULE 9B-72. | | | | 2) IF STORM PANELS ARE TO BE INSTALLED 2 COPIES OF A | | KEY PLAN AND AN INSTALLATION SCHEDULE WILL BE REQUIRED. | | THE WINDLOAD PRESSURES, ANCHOR TYPE AND SPACING, MOUNT | | TYPE, EDGE DISTANCE, SPAN, GLASS SEPARATION WILL | | REQUIRED. | | | | 3) THE SIMPSON CONNECTORS SPECIFIED FOR THE 4 X 4 PORCH | | APPEAR TO BE TYPOGRAPHICAL ERRORS. IT APPEARS THEY | | SHOULD BE ACE4 AND EPB44T. PLEASE CLARIFY. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|