Plan Review Notes For Permit 10060646
Permit Number 10060646
Review Stop B
Sequence Number 2
Notes
Date Text
2010-08-25 15:39:522007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR ROOF
 COVERING, HURRICANE CONNECTORS AND STRAPS, WINDOWS,
 STRUCTURAL MULLIONS AND IMPACT PROTECTION DEVICES AS
 REQUIRED BY DCA RULE 9B-72.
  
 2) IF STORM PANELS ARE TO BE INSTALLED 2 COPIES OF A
 KEY PLAN AND AN INSTALLATION SCHEDULE WILL BE REQUIRED.
 THE WINDLOAD PRESSURES, ANCHOR TYPE AND SPACING, MOUNT
 TYPE, EDGE DISTANCE, SPAN, GLASS SEPARATION WILL
 REQUIRED.
  
 3) THE SIMPSON CONNECTORS SPECIFIED FOR THE 4 X 4 PORCH
 APPEAR TO BE TYPOGRAPHICAL ERRORS. IT APPEARS THEY
 SHOULD BE ACE4 AND EPB44T. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW