2010-06-22 14:47:46 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | SIZING CALCULATIONS USING A CODE APPROVED METHOD AS | | REQUIRED BY FBC R M1401.3. | | | | 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE | | STRUCTURE. | | | | 3) SUBMIT 2 SETS OF MECHANICAL PLANS. SPECIFY THE | | SUPPLY AND RETURN DUCT SIZES, GRILL SIZES, LOCATIONS, | | CFMS. SPECIFY THE LOCATIONS OF THE AHU AND CONDENSER | | WITH REQUIRED DISCONNECTS AND SERVICE OUTLETS. SHOW | | COMPLIANCE WITH FBC R M1602.4 FOR BALANCED RETURN AIR. | | SPECIFY THE HVAC EQUIPMENT THAT WILL BE INSTALLED ON | | THE PLANS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|