Plan Review Notes
Plan Review Notes For Permit 10060646
Permit Number 10060646
Review Stop B
Sequence Number 1
Notes
Date Text
2010-06-22 16:52:472007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF STRUCTURAL PLANS FOR THE FRONT
 PORCH. SPECIFY ALL STRAPS AND CONNECTORS. SHOW THAT
 CONSTRUCTION COMPLIES WITH WINDLOADS AND THAT A
 CONTINUOUS LOAD PATH FROM THE ROOF TO THE FOUNDATION IS
 PROVIDED. SPECIFY ROOF PITCH, ROOF FRAMING, ROOF
 SHEATHING, SHEATHING FASTENERS & SPACING, ROOF
 COVERING, HEADER AND COLUMN SIZES AND ATTACHMENTS. SHOW
 ALL DIMENSIONS ON THE PLANS. SPECIFY THE DESIGN
 CRITERIA ON THE PLANS.
  
 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR ROOF
 COVERING, HURRICANE CONNECTORS AND STRAPS, WINDOWS,
 STRUCTURAL MULLIONS AND IMPACT PROTECTION DEVICES AS
 REQUIRED BY DCA RULE 9B-72.
  
 3) SUBMIT 2 COPIES OF A FLOOR PLAN SHOWING THE NEW
 WINDOW TYPES, SIZES AND LOCATIONS. INDICATE WHICH
 WINDOWS WILL BE MULLED TOGETHER. IDENTIFY THE ROOMS ON
 THE FLOOR PLAN, SUCH AS BEDROOM, BATHROOM, ETC.
  
 4) IF STORM PANELS ARE TO BE INSTALLED 2 COPIES OF A
 KEY PLAN AND AN INSTALLATION SCHEDULE WILL BE REQUIRED.
 THE WINDLOAD PRESSURES, ANCHOR TYPE AND SPACING, MOUNT
 TYPE, EDGE DISTANCE, SPAN, GLASS SEPARATION WILL
 REQUIRED.
  
 5) TWO COPIES OF A SURVEY OR SITE PLAN INDICATING THE
 DISTANCE TO PROPERTY LINES OF THE PORCH ARE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]