 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 230.7 OTHER CONDUCTORS IN RACEWAY OR CABLE.
 CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE
 INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE CABLE.
 ALL FEEDER AND BRANCH-CIRCUIT CONDUCTORS MUST BE
 SEPARATED FROM SERVICE CONDUCTORS. SERVICE CONDUCTORS
 ARE NOT PROVIDED WITH OVERCURRENT PROTECTION WHERE THEY
 RECEIVE THEIR SUPPLY; THEY ARE PROTECTED AGAINST
 OVERLOAD CONDITIONS AT THEIR LOAD END BY THE SERVICE
 DISCONNECT FUSES OR CIRCUIT BREAKERS. THE AMOUNT OF
 CURRENT THAT COULD BE IMPOSED ON FEEDER OR
 BRANCH-CIRCUIT CONDUCTORS, SHOULD THEY BE IN THE SAME
 RACEWAY AND A FAULT OCCUR, WOULD BE MUCH HIGHER THAN
 THE AMPACITY OF THE FEEDER OR BRANCH-CIRCUIT
 CONDUCTORS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  