Plan Review Notes For Permit 10060598
Permit Number 10060598
Review Stop Z
Sequence Number 2
Notes
Date Text
2010-07-15 09:24:11PLANNING AND ZONING: **** FAILED - COMMENTS NOT
 ADDRESSED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED MECHANICAL
 EQUIPMENT (GENERATOR AND LP TANK) TO ALL PROPERTY
 LINES. AS PER SECTION 94-305(B)(4) OF THE ZONING CODE
 ("ZLDR"): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK. SHOW GENERATOR TO
 SCALE ON SURVEY AND/OR A SCALED SITE PLAN. CLEARLY SHOW
 DIMENSIONS ON SURVEY. ALTHOUGH LP TANK WILL BE
 UNDERGROUND, THE SETBACKS AND ENCROACHMENT ALLOWANCE
 STILL APPLY.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT,
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  