Plan Review Notes For Permit 10060598 |
Permit Number |
10060598 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-07-23 08:33:48 | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} SUBMIT A SITE PLAN AND LOCATE ALL THE SERVICE AND | | GENERATOR GEAR ON SAME SO THAT COMPLIANCE WITH | | 230.72(GROUPING), 225.31-39 FOR THE DISCONNECTING MEANS | | REQUIREMENTS AND 250.32 FOR GROUNDING CAN BE REVIEWED. | | | | 2} 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY | | SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE | | SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE | | TIME.THE LOAD CALC'S ARE AT 70 AMPS, THE GENERATOR IS | | RATED FOR 65 AMPS. CORRECT THE LOADS. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | | | |
|