Plan Review Notes For Permit 10060582 |
Permit Number |
10060582 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-07-14 15:48:48 | ****PROVISO**** | | ****ISSUED AT CONTRACTOR'S RISK**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. ALL EXIT DOORS EXCLUDED FROM SCOPE OF WORK FOR THIS | | PERMIT. | | | | 2. AS DISCUSSED WITH CONTRACTOR, A REVISION IS REQUIRED | | IN ORDER TO INCLUDE DOORS IN THE SCOPE OF WORK. PROVIDE | | A LIFE SAFETY PLAN. SEE FBC 1003.6, MEANS OF EGRESS | | CONTINUITY. THE PATH OF EGRESS TRAVEL ALONG A MEANS OF | | EGRESS SHALL NOT BE INTERRUPTED BY ANY BUILDING ELEMENT | | OTHER THAN A MEANS OF EGRESS COMPONENT AS SPECIFIED IN | | THIS CHAPTER. OBSTRUCTIONS SHALL NOT BE PLACED IN THE | | REQUIRED WIDTH OF A MEANS OF EGRESS EXCEPT PROJECTIONS | | PERMITTED BY THIS CHAPTER. | | | | A MINIMUM OF TWO EXITS WHICH COMPLY WITH FBC CHAPTER 10 | | ARE REQUIRED: | | | | EXITS TO BE REMOTELY LOCATED (MINIMUM 1/2 THE DIAGONAL | | APART) | | TRAVEL DISTANCE TO BE 200' OR LESS TO THE NEAREST EXIT | | FROM ANY POINT IN THE BUILDING ALONG THE PATH OF TRAVEL | | | | |
|