Plan Review Notes For Permit 10060582 |
Permit Number |
10060582 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-07-06 09:10:33 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. DECLARE OCCUPANCY; OUR RECORDS SHOW THIS AS A2. | | | | 2. PROVIDE A LIFE SAFETY PLAN. SEE FBC 1003.6, MEANS OF | | EGRESS CONTINUITY. THE PATH OF EGRESS TRAVEL ALONG A | | MEANS OF EGRESS SHALL NOT BE INTERRUPTED BY ANY | | BUILDING ELEMENT OTHER THAN A MEANS OF EGRESS COMPONENT | | AS SPECIFIED IN THIS CHAPTER. OBSTRUCTIONS SHALL NOT BE | | PLACED IN THE REQUIRED WIDTH OF A MEANS OF EGRESS | | EXCEPT PROJECTIONS PERMITTED BY THIS CHAPTER. IT | | APPEARS THAT YOU PROPOSE TO BLOCK REQUIRED EXIT DOORS | | WITH SHUTTERS. | | | | ONE OF THE "EGRESS" DOORS SHOWN ON THE PLAN IS THE DOOR | | TO AN ELECTRIC ROOM (NO ACCESS FROM THE INSIDE OF THE | | BUILDING). ANOTHER IS A STORAGE ROOM, AND THE THIRD IS | | A KILN ROOM. HAVE THERE BEEN CHANGES TO THE FLOOR PLAN | | SINCE THE BUILDING WAS CONSTRUCTED? |
|