Plan Review Notes For Permit 10060562 |
Permit Number |
10060562 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-07-07 15:34:28 | 2017 BROWARD AVENUE | | PERMIT NUMBER 10060562 | | CHANGE INTERIOR DOORS TO STEEL 60 MIN. AS PER PLAN, ADD | | NEW EXTERIOR DOOR (SOUTH ELEV.) AND EXTERIOR STAIRS, | | ADD HALLWAY 2ND FLOOR | | | | | | 1. ALL RATED FIRE RATED DOORS ARE TO BE EQUIPPED WITH | | SELF-CLOSING DEVICES THAT CAUSE THE DOORS TO POSITIVELY | | LATCH WHEN CLOSED. | | | | 2. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS | | FOR HANDRAILS AND GUARDRAILS. | | | | 3. NO DETAILS PROVIDED REGARDING FIRESTOPPING METHODS | | FOR NEW RATED WALLS LOCATED ON THE SECOND FLOOR. | | | | 4. NO INFORMATION PROVIDED REGARDING THE TWO CLOSETS | | THAT ARE LOCATED IN THE MEANS OF EGRESS OF THE SECOND | | FLOOR. THESE CLOSETS ARE TO BE PROTECTED IF THEY ARE TO | | REMAIN WITHIN THE EXIT. | | | | 5. WHAT METHODS WILL BE USED FOR SLIP RESISTANCE FOR | | THE NEW STAIRS. | | | | 6. THE BUILDING IS LISTED AS AN R-1 OCCUPANCY. THE | | BUILDING IS BEING OPERATED AS A RESIDENTIAL BOARD AND | | CARE OCCUPANCY AND SHOULD BE LISTED AS R-4 OCCUPANCY. | | | | 7. THE CORRECT ADDRESS IS 2015 BROWARD AVENUE NOT 2017 | | SW BROWARD AVENUE. | | | | 8. BUILDING REVIEW COMMENTS PROVIDED REGARDING THE | | STAIRS, GUARD RAIL, AND HANDRAIL. | | | | 9. PLEASE REVISE PLANS AS NECESSARY. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|