2010-07-07 15:34:282017 BROWARD AVENUE
 PERMIT NUMBER 10060562
 CHANGE INTERIOR DOORS TO STEEL 60 MIN. AS PER PLAN, ADD
 NEW EXTERIOR DOOR (SOUTH ELEV.) AND EXTERIOR STAIRS,
 ADD HALLWAY 2ND FLOOR
  
  
 1. ALL RATED FIRE RATED DOORS ARE TO BE EQUIPPED WITH
 SELF-CLOSING DEVICES THAT CAUSE THE DOORS TO POSITIVELY
 LATCH WHEN CLOSED.
  
 2. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS.
  
 3. NO DETAILS PROVIDED REGARDING FIRESTOPPING METHODS
 FOR NEW RATED WALLS LOCATED ON THE SECOND FLOOR.
  
 4. NO INFORMATION PROVIDED REGARDING THE TWO CLOSETS
 THAT ARE LOCATED IN THE MEANS OF EGRESS OF THE SECOND
 FLOOR. THESE CLOSETS ARE TO BE PROTECTED IF THEY ARE TO
 REMAIN WITHIN THE EXIT.
  
 5. WHAT METHODS WILL BE USED FOR SLIP RESISTANCE FOR
 THE NEW STAIRS.
  
 6. THE BUILDING IS LISTED AS AN R-1 OCCUPANCY. THE
 BUILDING IS BEING OPERATED AS A RESIDENTIAL BOARD AND
 CARE OCCUPANCY AND SHOULD BE LISTED AS R-4 OCCUPANCY.
  
 7. THE CORRECT ADDRESS IS 2015 BROWARD AVENUE NOT 2017
 SW BROWARD AVENUE.
  
 8. BUILDING REVIEW COMMENTS PROVIDED REGARDING THE
 STAIRS, GUARD RAIL, AND HANDRAIL.
  
 9. PLEASE REVISE PLANS AS NECESSARY.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION