Plan Review Notes For Permit 10060551 |
Permit Number |
10060551 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-24 12:42:57 | *****PROVISO****** | | | | THE FIRE ALARM PLAN (FA 0.1 & FA 1.0) FIRE-STAMPED | | ACCORDINGLY; READY FOR PERMIT ISSUANCE. | | | | | | REVISED PLANS (THAT HAVE BEEN REVIEWED/APPROVED/STAMPED | | BY CSD) SHALL BE REQUIRED PRIOR TO THE FIRE ALARM FINAL | | - 302 WITH THE FOLLOWING CONDITIONS: | | | | 1. FIRE ALARM DEVICE IDENTIFYING NUMBERS LISTED IN THE | | FIRE ALARM RISER SHALL BE CLEAR AND READABLE. | | 2. AMEND NOTE #16 IN THE FIRE ALARM NOTES TO REFLECT | | THAT: DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL | | FIRE ALARM. | | 3. SMOKE DETECTORS SHOWN IN THE FIRE ALARM SYSTEM | | LAYOUT SHALL HAVE ITS OWN IDENTIFYING ADDRESS/NUMBER. | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|