2010-06-24 09:43:01PLUMBING REVIEW #1
 DENIED:
  
 SHEET P-1.0 -
 1. A DRINKING FOUNTAIN AND SERVICE SINK WILL BE
 REQUIRED FOR FACTORY/ BUSINESS OCCUPANCY.
 TABLE 403.1 MINIMUM NUMBER OF REQUIRED PLUMBING
 FIXTURES
 DRINKING FOUNTAIN-1 PER 100, 1 SERVICE SINK.
  
 2. SANITARY FROM SECOND FLOOR IS NOT PERMITTED TO FLOW
 THROUGH THE FIRST FLOOR FIXTURES.
 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF
 FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT.
  
 3. A VENT WILL BE REQUIRED BETWEEN OR UPSTREAM OF THE
 FIRST FLOOR WATER CLOSETS. THE LAV. STACK WOULD BE
 ACCEPTABLE AS A WET VENT.
  
 4. MINIMUM WATER PIPE SIZE IS 3/4" UP TO THE LAST TWO
 FIXTURES: TABLE 603.1
 604.1 GENERAL. THE DESIGN OF THE WATER DISTRIBUTION
 SYSTEM SHALL CONFORM TO ACCEPTED ENGINEERING PRACTICE.
 METHODS UTILIZED TO DETERMINE PIPE SIZES SHALL BE
 APPROVED. TABLE 603.1 SHALL BE PERMITTED TO BE USED TO
 SIZE THE WATER DISTRIBUTION SYSTEM.
  
 SHEET A2.1
 1. THE SECOND FLOOR RESTROOM DOES NOT APPEAR TO BE ADA
 ACCESSABLE.
 FBC 2007 11-4.1.3 ACCESSIBLE BUILDINGS:(11) TOILET
 FACILITIES. IF TOILET ROOMS ARE PROVIDED, THEN EACH
 PUBLIC AND COMMON USE TOILET ROOM SHALL COMPLY WITH
 SECTION 11-4.22.
  