Plan Review Notes For Permit 10060529 |
Permit Number |
10060529 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-06-24 09:43:01 | PLUMBING REVIEW #1 | | DENIED: | | | | SHEET P-1.0 - | | 1. A DRINKING FOUNTAIN AND SERVICE SINK WILL BE | | REQUIRED FOR FACTORY/ BUSINESS OCCUPANCY. | | TABLE 403.1 MINIMUM NUMBER OF REQUIRED PLUMBING | | FIXTURES | | DRINKING FOUNTAIN-1 PER 100, 1 SERVICE SINK. | | | | 2. SANITARY FROM SECOND FLOOR IS NOT PERMITTED TO FLOW | | THROUGH THE FIRST FLOOR FIXTURES. | | 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF | | FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME | | FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL | | WET VENT. | | | | 3. A VENT WILL BE REQUIRED BETWEEN OR UPSTREAM OF THE | | FIRST FLOOR WATER CLOSETS. THE LAV. STACK WOULD BE | | ACCEPTABLE AS A WET VENT. | | | | 4. MINIMUM WATER PIPE SIZE IS 3/4" UP TO THE LAST TWO | | FIXTURES: TABLE 603.1 | | 604.1 GENERAL. THE DESIGN OF THE WATER DISTRIBUTION | | SYSTEM SHALL CONFORM TO ACCEPTED ENGINEERING PRACTICE. | | METHODS UTILIZED TO DETERMINE PIPE SIZES SHALL BE | | APPROVED. TABLE 603.1 SHALL BE PERMITTED TO BE USED TO | | SIZE THE WATER DISTRIBUTION SYSTEM. | | | | SHEET A2.1 | | 1. THE SECOND FLOOR RESTROOM DOES NOT APPEAR TO BE ADA | | ACCESSABLE. | | FBC 2007 11-4.1.3 ACCESSIBLE BUILDINGS:(11) TOILET | | FACILITIES. IF TOILET ROOMS ARE PROVIDED, THEN EACH | | PUBLIC AND COMMON USE TOILET ROOM SHALL COMPLY WITH | | SECTION 11-4.22. | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | | | | | |
|